Installation Instructions
Installation Instructions
Document No. 129-609
September 26, 2017
Series
2200
/3200
Room
Units
for
Programmable BACnet Terminal
Equipment Controllers (TECs)
Item Number 129-609, Rev. FA Page 1 of 3
Product Description
The Series 2200 and 3200 room units allow users to
measure and communicate temperature, humidity,
and carbon dioxide values to a Programmable
BACnet TEC Zone Controller (PTEC). Local viewing
of the measured values and temperature setpoint
adjustment are also possible through the room unit's
buttons and digital display.
These devices work with all PTECs. They
incorporate a solid state or sensing element to
detect temperature, as well as a CO
2
module for
carbon dioxide measurement. Relative humidity
measurement is also possible with some models.
The effective temperature sensing and setpoint
range is 55°F to 95°F (13°C to 35°C). CO
2
is
measured over the range of 0 to 2000 parts per
million (PPM). The relative humidity measuring
range is 0 to 100%.
The room units communicate with the TEC using a
6-wire RJ-11 cable. A tool port is located at the
bottom of the sensor housing for connecting the
Siemens WCIS software or the Passkey
Configuration Tool.
Hardware is included for installation on drywall or on
a 2” × 4” electrical box.
Product Numbers
QAA2280.xWxC Temperature only
QFA3280.xWxC Temperature and Humidity
QPA2282.xWxC Temperature and CO
2
QPA2284.xWxC Temperature, Humidity,
and CO
2
Caution Notations
CAUTION:
Equipment damage or loss of
data may occur if you do not
follow a procedure as
specified.
Expected Installation Time
20 minutes
Figure 1. CO
2
Room Unit.
Accessories
AQM3060 Replacement RH sensing
element (QPA only)
AQM2200 Power Module
(Required for QPA)
AQA2200-INTL Room Unit Back Plate (10-pack)
544-643A Passkey HMI Configuration Tool
563-102 GSKT KIT Room Sensor Insulating
Gasket (10-pack)
(For hollow wall installations)
588-100A 25-foot cable with connectors
588-100B 50-foot cable with connectors
588-100C 100-foot cable with connectors
Required Tools
• Phillips sizes 1 and 2 screwdrivers
• Small and medium, flat-blade screwdrivers
• 1/16-inch hex key or 544-643A Passkey
(includes hex bit)
• Medium-duty electric drill
• 3/16-inch (4.8 mm) drill bit
• One-inch (25 mm) hole saw
• Small level
• Tape measure
• Marker or pencil
If using non-terminated or damaged cables, you also
need:
• Room unit connector tool (RJ-11 crimping
tool – 540-140 or third-party tool)
• Room unit connector kit (540-141)