Siemens Wall-mounted sensors and room operator units for KNX/ETS and KNX/ACS CM2N1602en_06
Building Technologies Functionality / Use 2019-04-08
4.3 Display elements and buttons
Button
Button
1
2
3
4
5
6
7
8
An arrow indicates that an element can be operated
Temperature display in °C or °F / humidity in % r.H. /
air quality in text, symbol, or ppm of CO
2
Toggling (key 1) between indoor and outdoor measurement
(temperature, humidity, CO2)
Indication that a window is open (connected window switch is active)
Display of the plant state (Heating or Cooling / inactive)
Note: No manual switchover!
Display of the relative or absolute setpoint for temperature (Comfort)
Setpoints for room humidity and room CO
2
concentration.
Adjusting the setpoint using keys 2 and 6
Display of the present fan speed (when automatic)
Adjusting the fan speed using key 3 (or keys 3 and 7 if operation of room
operating mode is disabled)
Display of the room operating mode (when automatic)
Adjusting the room operating mode using key 7
Navigation: toggle the display / setpoint setting between temperature /
humidity / CO
2
, using key 4. The black bar points to the displayed
information.
Operation of the occupancy state (presence switch, Comfort extension)
Activate the Comfort extension using key 8 (only available if enabled)
Engineering functions (press keys 1 and 8 simultaneously during 5 s)
Programming mode (key 2), same function as programming pin
(service pin) on the back of the device
Connection test (Key 3) (not supported by ETS and ACS)
Reset device to factory settings (key 4)
NOTICE This operation is irreversible!
Indicates that the room operator unit is locked by the system.
Operation is disabled
The display in line 1 shows the temperature from bus
A
B