Siemens Wall-mounted sensors and room operator units for KNX/ETS and KNX/ACS CM2N1602en_06
Building Technologies ETS engineering 2019-04-08
Obj.
Object name Function
Type / Length
Fla gs
QMX3.P30
QMX3.P40
QMX3.P70
QMX3.P34
QMX3.P74
QMX3.P02
QMX3.P37
Room humidity sensor
25 Room relative humidity [%]
relative room humidity in %
9.007
2 bytes
CRWU
X
X
X
Room humidity control
26 Switching point r.h. - stage 1 relative humidity in %
9.007
2 bytes
CRWU
X X X X X X X
27 Switching point r.h. - stage 2
relative humidity in %
9.007
2 bytes
CRWU
X X
X
X X
X
X
28
Switching point r.h. - stage 3 relative humidity in %
9.007
2 bytes
CRWU
X
X
X X
X
X
X
29 Control value r.h. cont. - manual setp. Setpoint in 0 to 100%
5.001
1 byte
CRWU
X X X X X X X
30 Control value r.h. cont. - manual mode Manual/Auto mode
1.003
1 bit
CRWU
X X X X X X
X
31
Enable room r.h. controller On/Off
1.003
1 bit
CRWU
X
X X X X X X
32
Override room r.h. controller Ventilation (Boost) on/off
1.003
1 bit
CRWU
X X
X X X X X
33
Control value r.h. stage 1 - on/off 1 = On / 0 = Off
1.001
1 bit
CRT
X X X X X X X
34 Control value r.h. stage 2 - on/off 2 = On/0 = Off
1.001
1 bit
CRT
X
X X X X X X
35
Control value r.h. stage 3 - on/off 3 = On/0 = Off
1.001
1 bit
CRT
X
X X X X X X
36 Control value r.h. - cont 0 - 100%
5.001
1 byte
CRT
X X X
X X X X
Provides the room humidity value from the integrated sensor.
Units with display: Must be placed in a group address to display operation/symbol on the display.
External room humidity sensor values, see object 70
External outside humidity sensor values, see object 69
The configured default switching points apply as long as no value is received from the bus.
In manual mode (obj. 30, 1=Manual), a setpoint is received via this object and outputted directly as modulating positioning
signal (object 36).
Changing over to the manual mode permits receipt of a manual setpoint (Obj. 29) for the modulating positioning signal
(Obj. 36). Otherwise, the configured positioning signals for the applicable stage are outputted.
All controller outputs are switched off upon receipt of "Controller off".
The controller remains disabled until "Controller on" is received. The default value is controller on = 1.
For controller override, the stage defined in the parameter "Stage is overridden" is enabled. Objects 33, 34, 35 assume
only the value "1=On" for the corresponding object; the other two objects the value "0 = Off". The modulating positioning
signal (obj. 36) outputs the value configured for the applicable stage.
Override has the highest priority. The default state is "Normal".
The stage belonging to positioning signal r.h. is switched on if room humidity overrides a
switching point r.h. The positioning signal r.h. is switched off again for room humidity <
switching r.h. - hysteresis.
The positioning signal configured for the stage is outputted if room humidity overrides a
switching point r.h. The positioning signal once again outputs the value of the next smaller
stage, for room humidity < switching r.h. - Hysteresis.
Devices
Off
Pos. Signal stage 3
Pos. signal stage 2
Pos.signal stage1
On
[ppm CO2]
[% r.H.]
1411D01
Swithing
point stufe
1
Switching
point 2
Switching
point 3
Hysteresis
On
On
Off
Off
[ppm CO2]
[% r.
H.]
[%]
Pos
. Sig. Stage
0
Pos. signal stage 1
Pos. signal stage 2
Pos., signal
modulating
Pos.
signal stage 3
Hysteres
is
1411D02
Switching
point
stage 1
Switching
point
stage 2
Switching
point
stage 3