Siemens Wall-mounted sensors and room operator units for KNX/ETS and KNX/ACS CM2N1602en_06
Building Technologies ETS engineering 2019-04-08
*
PID parameter set for the heating sequence
Heating type
Xp
TiN
TiV
Nz
SD
Radiator heating slow
2 K
5400s
450s
0,1K
0.8K
Radiator heating fast
2 K
3600s
540s
0,1K
0.8K
Floor heating slow
2 K
7200s
540s
0,1K
0.8K
Floor heating fast
2 K
5400s
540s
0,1K
0.8K
PID parameter set for the cooling sequence
Cooling type
Xp
TiN
TiV
Nz
SD
Chilled ceiling
2 K
5400s
450s
0,1K
0.8K
Floor cooling 2 K 5400s 540s 0,1K 0.8K
Regardless of the setting of the control signal type "PWM" or "continuous", all 4
objects are switched on. The option "Do not send cyclically" is not operable for the
moment.
Note