Data Sheet for Product

2/4
Siemens Indoor air quality sensors QPA10x4 A6V101099173_en--_b
Building Technologies 2018-05-01
Engineering notes
The sensor must be powered by a transformer for safety extra low-voltage (SELV) with
separate windings, suited for 100 % duty.
On applications with EMC problems, use shielded cables. For secondary power lines
and signal lines, use twisted-pair cables.
Mounting notes
Inner wall of the room to be ventilated, not in niches, not behind curtains, not above or
near heat sources, and not exposed to direct light from spot lights.
Do not expose the sensor to direct solar radiation.
Seal the end of the conduit at the sensor to prevent false measurements due to drafts
through the conduit.
Mounting instructions are enclosed in the package.
Disposal
The device is considered electrical and electronic equipment for disposal in terms of the
applicable European Directive and may not be disposed of as domestic garbage.
· Dispose of the device through channels provided for this purpose.
· Comply with all local and currently applicable laws and regulations.
Technical data
Operating voltage
AC
24 V ± 20 % or DC 15…35 V (SELV)
or
AC
/DC 24 V class 2 (US)
Frequen
cy
5
0 / 60 Hz at AC 24 V
External supply line protection (EU)
max. 10 A or
Circuit breaker
max. 13 A
Characteristic B, C, D according to EN 60898 or
Power source with
current limitation of
max. 10 A
Power consumption
At "U" output signal
Max. <0.9 VA
"I" output signal
Max. <3.2 VA
Measuring range 0...2000 ppm
Measuring accuracy at 23 °C and 1013 hPa £± (60 ppm + 4 % of measured value)
Long time drift £±7 % of measuring range / 5 years
(typically)
Output signal, linear (terminal X1) 4...20 mA 0...2000 ppm, max. 500 Ohm
DC 0...10 V 0...2000 ppm, max. ± 1 mA
Recalibration free 8 years
Measuring range 0...50 °C
Measuring accuracy at DC 24 V and 23 °C ± 0.5 K
Output signal, linear (terminal X2) 4...20 mA 0...50 °C, max. 500 Ohm
DC 0...10 V 0...50 °C, max. ± 1 mA
Protection degree of housing IP30 according to EN 60529
Protection class III according to EN 60730-1
Screw terminals for 1´ 2.5 mm
2
or 2´ 1.5 mm
2
Operation to
Climatic conditions
Temperature (housing incl. electronics)
Humidity
Mechanical conditions
IEC 60721-3-3
Class 3K3
0...50 °C
0…95 % r. F (non condensing)
Class 3M2
Cable routing and
cable selection
Mounting location
Mounting instructions
Power supply
Cable lengths for measuring
signal
Functional data "CO
2
"
Functional data "Temperature"
with
QPA1064
Degree of protection
Electrical connections
Environmental conditions