User Manual

Siemens Building Technologies CM1N5483E / 10.1998
Landis & Staefa Division 5/8
avoid damage when fitting, the bar on the detector and the terminal block on the
power part must oppose one another with the inscriptions on both unit sections mirror-
inverted. Caution: Do not exert any pressure on the pyramid-shaped plastic insert
(optics) of the unit!
After applying the operating voltage or after fitting the detector, the unit will be
switched on for 1.5 min (initialization phase), that is, the lighting and HVAC outputs
are deactivated. This is followed by a 9-minute service phase. During that phase, the
output for lighting responds with no delay if the brightness changes. During this period
of time, the proper functioning of the lighting circuitry can be checked by darkening
the space or by pointing a torchlight at the sensor.
The switch off delay facility for the lighting system is self-learning. It is adapted to the
frequency of movement of people present in the space and, after the movement
detected last, is 5 to 15 minutes (refer to «Functions»).
The HVAC switch on delay starts when the first movement is detected.
The HVAC switch off delay starts after the last movement is detected.
If the detection zone of a detector interferes with that of another detector, the part of
the detector that should not monitor the area of the other detector must be covered
with an adhesive type that is impervious to light.
If there are too many false switching operations, caused by an unfavourable location of
the unit, the potentiometer for the HVAC switch on delay must be set to «N».
This means:
Switch off delay «Lighting»: 15 min, fixed
Switch on delay «HVAC»: 0 s, fixed
Operating voltage AC 230 V ± 10 %
Frequency 50 or 60 Hz
Power consumption
Idle state 0.5 VA
Contact closed 1.5 VA
Control output for lighting
Relay contact (N.O.), non-potential-free AC 230 V
Rating
with fluorescent lamps 8 A max.
with incandescent lamps 5 A max.
Switch off delay (self-learning) 5...15 min
Daylight control automatic off switching
Min. brightness (adjustable) 50...1600 Lux
HVAC control output
Relay contact (N.O.) potential-free
Rating 2 A max. at AC 230 V
5 mA min. at DC 5 V
3.75 kV isolated
against mains
Switch on delay (adjustable) 0...300 s
Switch off delay (adjustable) 0.5...30 min
Detection of movements
Optics Fresnel lens
Sensing elements 4 pyroelectric sensors
Sensitivity (seated people) typically 25 cm body movement
Surveillance angle 360° volumetric
Detection zone
Seated people 5 x 5 m (installation height 2.5 m)
7 x 7 m (installation height 3 m)
Walking people 8 x 8 m (installation height 2.5 m)
10 x 10 m (installation height 3 m)
Emergency operation
Technical data