Data Sheet for Product

Technical Instructions QPM Series Indoor Air Quality Duct Sensors
Document Number CE1N1962
July 26, 2019
Page 6 Siemens Industry, Inc.
Mounting Notes
Mounting Location and
Orientation
To ensure degree of protection, mount the sensor with the cable entry pointing
downward.
Mount the sensor in a location where it can be easily accessed for service.
If used in connection with steam humidifiers, the distance to the humidifier must be
a minimum of 9.8 feet (3 m). If permitted by the installation, the distance should be
as great as possible, but no more than 32.8 feet (10 m).
Handle carefully; the sensing elements in the immersion rod are susceptible to
impact and shock.
The sensor must not be mounted in a ventilation application on top of a building
(impact of solar radiation). To ensure correct operation, the sensor’s ambient
temperature must be between 23°F to 113°F (5°C to 45°C).
Commissioning
Notes
Check the sensor’s functions 30 minutes after applying power.
Checking the CO
2
function:
In well-ventilated spaces, the sensor shows the CO
2
concentration of the outside air.
Typically, this is 360 ppm (depending on the sensor’s measuring accuracy). Also, a
basic functional check can be made by exhaling on the sensor. Note that the
sensor’s rate of response has been purposely delayed (time constant t
90
=
5 minutes).
Checking the VOC function:
Touch the sensor with a cotton ball dowsed in alcohol.
Ventilation should start when the preset switching level of the connected controller
is reached.
After applying power to sensors with display, Init will appear for approximately six
seconds.
Specifications
Power supply
Operating voltage (SELV) 24 Vac 20% or 15 to 35 Vdc
Frequency 50/60 Hz at 24 Vac
Power consumption 2 VA
Functional data, CO
2
Measuring range (MV = measured value) 0 to 2000 parts per million (ppm) *
Measuring accuracy @ 73°F (23°C) < + (50 ppm + 2% MV)
and 1013 hPa
Temperature dependency in 23°F to 113°F + 2 ppm/°C typically
(-5°C to 45°C) range
Long-time drift < + 5% measuring range/5 years
Time constant t
90
<5 minutes
Output signal, linear (terminal X1) 0 to 2000 ppm
Recalibration Not required for 8 years
* Allow up to 96 hours for unit to reach published accuracy.
Functional data,
maximum selection of
CO
2
and VOC with
QPM2102/QPM2102D
Measuring range VOC 0 to 2000 ppm
VOC sensitivity See Table 1
Output signal, linear (terminal X2) 0 to 2000 ppm
Response time, VOC signal t
voc
3 minutes/V