3 RDF301 RDF600KN RDF600KN/VB RDF301.50 RDF600KN/S Semi flush-mount communicating room thermostats 171 RDF301.50H RDF301 RDF301.50..
· AC 230 V operating voltage · User and parameter settings can be retained or restored with power loss Additional RDF600KN, RDF600KN/VB features: · Independent function for window contact, presence detector (standard presence and hotel presence) Additional RDF600KN/S features: · Independent function for window contact, presence detector (standard presence and hotel presence) · Four buttons to control KNX actuators via KNX S-mode (functions: switching, dimming, blinds control, 8-bit scene) Additional RDF301.
Functions · Room temperature control via built-in temperature sensor or external room temperature / return air temperature sensor. · Changeover between heating and cooling mode (automatically via local sensor or bus, or manually). · Selection of applications via DIP switches or commissioning tool. · Selection of operating mode via operating mode button on the thermostat. · Temporary Comfort mode extension. · 1-speed or 3-speed fan control (automatically or manually).
Applications The thermostats support the following applications, which can be configured using the DIP-switches on the inner side of the thermostat's front panel or a commissioning tool. Remote configuration All DIP switches need to be set to OFF (remote configuration, factory setting) to select an application via commissioning tool. Remote configuration, via commissioning tool (factory set) · Synco ACS · ETS DIP switches ON 1 2 3 4 / 20 Siemens Smart Infrastructure RDF301, RDF301.50...
Applications for fan coil systems Application and output signal, DIP switches, diagram ON · 2-pipe fan coil unit (heating or cooling) ON ON/OFF 2 3 1 2 3 2 3 3171D21 3076D20 1 · 2-pipe fan coil unit with el.
Applications for Universal systems* Application and output signal, DIP switches, diagram ON 1 2 3 3191S11 B2 ON/OFF D3 T · Chilled / heated ceiling with electric heater (heating or cooling) ON/OFF B2 D3 T Y1 2 3 2 3 Y1 T T T B1 B1 YE N1 T N1 ON 3-position 1 2 3 · Chilled ceiling and radiator ON/OFF (heating and cooling) 3191S11 D3 T Y1 1 D3 Y1 T Legend ON 3191S13 · Chilled / heated ceiling (heating or cooling) B2 1 3191S12 · Chilled / heated ceiling (heating or
Applications for heat pump systems Application and output signal, DIP switches, diagram ON ON ON/OFF 2 3 3181S31 1 D3 · 1-stage compressor with electric heater (heating or cooling) ON/OFF 1 2 3 3181S32 · 1-stage compressor (heating or cooling) D3 T T B1 B1 YE T T N1 N1 ON · 1-stage compressor (heating and cooling) ON/OFF 2 3 3181S35 1 D3 T B1 T Legend N1 Thermostat YE Electric heater N1 B1 Return air temperature sensor or external room temperature sensor (optional) D3 Dewp
Product no. RDF301 RDF301.50 4) RDF301.50H 3) RDF600KN RDF600KN/VB RDF600KN/S 4) Operating voltage Stock no. S55770-T104 S55770-T105 S55770-T334 S55770-T293 S55770-T430 S55770-T400 AC 230 V AC 230 V AC 230 V AC 230 V AC 230 V AC 230 V Control outputs 3-pos ON/OFF 1 1) 1 1) 1 1) 1 1) 1 1) 1 1) 2 1) 2 1) 2 1) 2 1) 2 1) 2 1) Suitable conduit box 2) Type summary Color square square square round or square round or square round or square 1) Selectable: on/off or 3-position. 2) Square conduit box e.
3-position actuators Electrical actuator, 3-position (for radiator valve) Electrical actuator, 3-position (for 2- and 3-port valves / V…P45) Electrical actuator, 3-position (for small valve 2.5 mm) Electrical actuator, 3-position (for small valve 5.5 mm) SSA31... 4893 Electrical actuator, 3-position SAS31… 4581 SSC31 4895 SSP31… 4864 SSB31... 4891 *) The documents can be downloaded from http://siemens.com/bt/download.
Mechanical design The thermostats consist of 2 parts: · Front panel with electronics, operating elements and built-in room temperature sensor. · Mounting base with power electronics. The rear of the mounting base contains the screw terminals. Slide the front panel in the mounting base and snap on. Operation 1 and settings 1 2 1 2 4 2 5 4 3 3 5 3 RDF301, RDF600KN, RDF301.50, RDF600KN/S RDF600KN/VB 1 Operating mode selector RDF301.
Engineering notes See "Reference documentation" on page 16 for information on how to engineer the KNX bus (topology, bus repeaters, etc.) and how to select and dimension connecting cables for supply voltage and field devices. Mounting and installation Mount the room thermostat on a conduit box. Do not mount on a wall in niches or bookshelves, behind curtains, above or near heat sources, or exposed to direct solar radiation. Mount about 1.5 m above the floor.
Commissioning notes Applications The room thermostats are delivered with a fixed set of applications. Select and activate the relevant application during commissioning using one of the following tools: - Local DIP switch and HMI - Synco ACS - ETS Set the DIP switches before snapping the front panel to the mounting plate, if you want to select an application via DIP switches. All DIP switches need to be set to "OFF" ("remote configuration"), if you want to select an application via commissioning tool.
Control parameters The thermostat's control parameters can be set to ensure optimum performance of the entire system (see basic documentation P3171). The parameters can be adjusted using - Local HMI - Synco ACS - ETS Control sequence · The control sequence may need to be set via parameter P01 depending on the application. The factory setting for the 2-pipe application is "Cooling only"; and "Heating and Cooling" for the 4-pipe application.
Technical data Power supply Caution Outputs STOP Note! Caution Inputs KNX bus Operational data Rated voltage AC 230 V Overvoltage category III Frequency 50/60 Hz Power consumption RDF301... Max. 4 VA / 3.0 W RDF600KN… Max. 3.5 VA / 1.2 W No internal fuse External preliminary protection with max C 10 A circuit breaker required in all cases AC 230 V Fan control Q1, Q2, Q3-N Min. 5 mA, Max.
Environmental conditions Standards and directives Environmental Compatibility General Built-in room temperature sensor Measuring range Accuracy at 25 °C Temperature calibration range Settings and display resolution Setpoints Current temperature value displayed Storage Climatic conditions Transport Climatic conditions Operation Climatic conditions EU conformity (CE) RDF301... RDF600KN… Electronic control type 0…49 °C < ± 0.5 K ± 3.0 K 0.5 °C 0.
Reference documentation Handbook for Home and Building Control - Basic Principles (https://my.knx.
Application L AC 230 V 10 A L KNX S1 S2 B1 B2 X1 M CE+ CE- X2 Y21 N1 Y11 N Q1 Q2 Q3 I II III 2-pipe, 2-position M1 N 3171A12 Connection diagrams Y1 N1 M1 Y1 Y1, Y2 E1 C1, C2 S1, S2 5(2)A 5(2) A max . max . B1, B2 2-pipe, 3-position - Y11 = Open - Y21 = Close 2-pipe and electric heater Y1 5( 2)A max. Y1 5(2)A max. 4-pipe - Y1 = Heating - Y2 = Cooling 1-stage compressor - C1 = Heating and / or - C2 = Cooling) 1-stage compressor and electric heater CE+ CEE1 5( 2)A max.
Dimensions Dimensions in mm RDF600KN… 3076M01 86 RDF301... 16 30 80 3076M13_01 14 3076M12 3171M13 86 18 / 20 Siemens Smart Infrastructure RDF301, RDF301.50...
/ 20 Siemens Smart Infrastructure RDF301, RDF301.50...
Issued by Siemens Switzerland Ltd Smart Infrastructure Global Headquarters Theilerstrasse 1a CH-6300 Zug Tel. +41 58 724 2424 www.siemens.com/buildingtechnologies © Siemens Switzerland Ltd, 2009 - 2020 Technical specifications and availability subject to change without notice. 20 / 20 Siemens Smart Infrastructure RDF301, RDF301.50...