s RDF301, RDF600KN RDF301.50 Semi-flush mount room thermostats with KNX communications RDF301, RDF301.50, RDF600KN Basic Documentation Edition: 2.
Contents 1. About this document ..............................................................................4 1.1 Revision history.........................................................................................4 1.2 Reference documents ...............................................................................4 1.3 1.3.1 1.3.2 1.3.3 Before you start .........................................................................................5 Copyright .....................................
.11.5 3.11.6 3.11.7 3.11.8 3.11.9 Send heartbeat and receive timeout.......................................................50 Startup.....................................................................................................50 Heating and cooling demand ..................................................................50 Fault function on KNX .............................................................................51 KNX switching groups (RDF301.50 only) .....................................
1. About this document 1.1 Revision history Edition Date Changes Section Pages 2.0 1.0 Oct 2012 22 Jun 2010 Added RDF600… First edition All All 1.2 Reference documents Subject Semi-flush mount room thermostats with KNX communications, RDF301, RDF301.50, RDF600KN KNX Manual Ref [1] [2] [3] [3a] Doc No. Description CE1N3171 Data Sheet CE1B3171... Operating Instructions CE1M3171 Mounting Instructions RDF301... CE1M3076.1 Mounting Instructions RDF600KN [4] Synco and KNX (see www.siemens.
1.3 Before you start 1.3.1 Copyright This document may be duplicated and distributed only with the express permission of Siemens, and may be passed only to authorized persons or companies with the required technical knowledge. 1.3.2 Quality assurance This document was prepared with great care.
1.4 Target audience, prerequisites This document assumes that users of the RDF KNX thermostats are familiar with the ETS and/or Synco ACS tools and able to use them. It also presupposes that these users are aware of the specific conditions associated with KNX. In most countries, specific KNX know-how is conveyed through training centers certified by the KNX Association (see www.konnex.org/). For reference documentation, see section 1.2. 1.
Summary 2.1 Types Operating voltage Product no. Stock no. Control outputs 3-pos RDF301 RDF301.50 RDF600KN S55770-T104 S55770-T105 S55770-T293 AC 230 V AC 230 V AC 230 V ON/OFF DC 0..10 V 1 1) 1 1) 1 1) 2 1) 2 1) 2 1) KNX switching groups ---- Suitable conduit box 2) 2. rectangular rectangular round 1) Selectable: ON/OFF or 3-position 2) Rectangular conduit box e.g. ARG71. Round CEE conduit box min 60 mm diameter and min 40 mm depth 2.
Features Type of mounting / suitable conduit boxes RDF600KN for round CEE box, with min 60 mm diameter, min 40 mm depth RDF301… for recessed rectangular box with 60.3 mm fixing centers Functions Room temperature control via built-in temperature sensor or external room temperature / return air temperature sensor Changeover between heating and cooling mode (automatic via local sensor or bus, or manually) Selection of applications via DIP switches or commissioning tool (ACS).
2.4 Integration via KNX bus The RDF room thermostats can be integrated as follows: Integration into Synco 700 system via LTE mode (easy engineering) Integration into Synco living via group addressing (ETS) Integration into Desigo and Apogee via group addressing (ETS) or individual addressing Integration into third-party systems via group addressing (ETS) The following KNX functions are available: Central time program and setpoints, e.g.
Synco topology Legend: Synco 700 Synco living RDG..., RDF…, RDU… OZW772 (or OZW775) RMZ792 QAW... ACS RXB, RXL QAX Desigo, Apogee and third-party systems Building automation and control system (BACS) Room automation and control system Room thermostats Web server Bus operator unit Room unit Service tool using OCI700.1 (OCI700.
2.5 Equipment combinations Description On / off actuators Product no. Data sheet Cable temperature sensor QAH11.1 1840 Room temperature sensor QAA32 1747 Condensation detector / extension module QXA2000 / QXA2001 / AQX2000 1542 Electromotoric ON/OFF actuator SFA21... 4863 Electromotoric ON/OFF valve and actuator MVI… / MXI… 4867 SUA… 4832 STA23... STA21... *) STP23... STP21... *) 4884 4893 *) 4884 4893 *) SSA31... 4893 SSP31… 4864 SSB31... 4891 SSD31...
3. Functions 3.1 Temperature control General note: Parameters Setting of the control parameters (P01, etc., mentioned throughout the document) is described in section 3.13. Temperature control The thermostat acquires the room temperature via built-in sensor, external room temperature sensor (QAA32), or external return air temperature sensor (QAH11.1), and maintains the setpoint by delivering actuator control commands to heating and/or cooling equipment.
3.2 Operating modes The thermostat's operating mode can be influenced in different ways (see below). Specific heating and cooling setpoints are assigned to each operating mode. K NX R Room operating mode: State The thermostat sends the effective room operating mode on the bus. The following operating modes are available: Auto Timer In Auto Timer mode the room operating mode is commanded via bus.
3.2.1 Source for change of operating mode ACS Source Local operation via operating mode button Bus command K NX R Room op. mode The operating mode can be influenced by different interventions. The source of the effective room operating mode state can be monitored using the "Cause" diagnostic data point in the ACS tool, operator unit RMZ792 or web server OZW772 / 775.
Auto Timer mode with time schedule via bus If a time schedule via bus is present, e.g. from central control unit, then the Auto Timer mode is active. The thermostat automatically changes between Comfort and Economy according to the time schedule via bus. The display shows the Auto Timer mode symbol along with the symbol for the effective room operating mode (Comfort or Economy ). By pressing the operating mode button, you can change to another operating mode.
Temporary timer to extend the Comfort mode Comfort mode can be temporarily extended (e.g. working after business hour or on weekends) when the thermostat is in Economy mode. The operating mode button switches the operating mode back to Comfort for the period preset in P68. Press the operating mode button again to stop the timer.
3.2.2 Communication examples The following examples show two typical applications of a central time schedule in conjunction with local control of the room operating mode. The room operating mode in rooms 1…2 of a building is determined by the time schedule. Window contacts are fitted in all rooms.
Interaction of user operation (operating mode button) and central time schedule Example 2 In room 2, the window is opened briefly, once in the morning and once at night (1). Only the opening in the morning has a direct impact on the effective room operating mode. With the operating mode button, the operating mode can be changed between OFF and Auto or temporary Comfort extension respectively. Time schedule Room operating mode During lunch break, the time schedule changes to Precomfort.
Comfort mode 3.3 Room temperature setpoints 3.3.1 Description The factory setting for the Comfort basic setpoint is 21 °C and can be changed in the thermostat’s EEPROM via parameter P08 or via bus with communication object " Comfort basic setpoint". The last intervention always wins. The Comfort setpoint can be adjusted via the +/- buttons, or via bus from a remote device like a touchpanel, operating unit, etc. The last intervention always wins.
Economy mode Use control parameters P11 and P12 to adjust the Economy mode setpoints. The heating setpoint is factory-set to 15 °C, and the cooling setpoint to 30 °C. Protection mode Use control parameters P65 and P66 to adjust the Protection mode setpoints. The heating setpoint is factory-set to 8 °C (frost protection) and to OFF for cooling. Caution If a setpoint (Economy or Protection) is set to OFF, the thermostat does not control the room temperature in the corresponding mode (heating or cooling).
3.3.
General notes: The supported communication objects are different in LTE mode and S-mode Changes via the local HMI or via tool have the same priority (last always wins) Setting the Comfort basic setpoint will reset the runtime Comfort setpoint to the basic setpoint Notes on setpoint adjustment (LTE mode with Synco only) Central setpoint shift is used for summer / winter compensation in particular Setpoint shift does not affect the setpoints stored in parameters P08, P11, P12, P33 Local shift a
3.4 Applications overview The thermostats support the following applications, which can be configured using the DIP switches inside the front panel of the unit or a commissioning tool. All DIP switches need to be set to OFF (remote configuration, factory setting) to select an application via commissioning tool. The tool offers the applications printed in bold text (basic applications). For universal applications (chilled ceiling, etc.), refer to section 3.6.6.
Heating and cooling 4-pipe fan coil unit (heating and cooling) ON/OFF Chilled ceiling and radiator (heating and cooling) ON/OFF 1-stage compressor (heating and cooling) ON/OFF DIP switches Diagram ON 3076D22 Application and output signal 1 2 3 Y2 T (B1) Y1 M1 T (B1) Key Y1 Heating or heating / cooling valve actuator Y2 Cooling valve actuator YE Electric heater M1 3- or 1-speed fan B1 Return air temperature sensor or external room temperature sensor (optional) B2 Changeover sensor (option
3.5 Additional functions Heating / cooling changeover via bus The heating / cooling changeover information can be received via bus. This is only possible if the control sequence is set to automatic heating / cooling changeover (parameter P01 = 3) and no local input X1, X2 is assigned with this function. K NX In the absence of the required information (e.g. due to problems with data communication, power failure, etc.), the thermostat operates in the last valid room operating mode (heating or cooling).
The changeover sensor ensures changeover from heating to cooling mode based on the acquired water temperature. We recommend activating the “Purge” function (parameter P50) with 2-port valves. This function ensures correct acquisition of the medium temperature even if the 2-port valve is closed for an extended period of time. The valve is then opened for 1 to 5 minutes (adjustable) at 2-hour intervals during off hours.
The “Floor temperature limitation” function influences the outputs listed in the table below: “Floor temp. limit” function has impact on Application Output Y11 2-pipe H/C valve 2-pipe & el heater H/C valve 4-pipe Output Y21 El heater Heating valve Cooling valve Heating (P01 = 0/2/3) Cooling Heat. and cool.
3.6 Control sequences 3.6.1 Sequences overview (setting via parameter P01) The main control sequence (i.e. the water coil sequence of the fan coil unit) can be set via parameter P01. The following sequences can be activated in the thermostats (each without or with auxiliary heating). The available sequences depend on the application (selected via DIP switch, see section 3.4). Parameter P01 = 0 P01 = 1 P01 = 2 P01 = 3 P01 = 4 T Sequence T °C T °C Heating Cooling *) 2-pipe with el.
3.6.2 K NX Application mode The behavior of the thermostat can be influenced by a building automation and control system (BACS) via bus with the command “Application mode”. With this signal, cooling and/or heating activity can be enabled or disabled. Application mode is supported in LTE mode and S-mode.
ACS Heating OR cooling The state (heating or cooling) of the thermostat can be monitored with the ACS tool (diagnostic value “Control sequence”). The last active mode is displayed when the thermostat is in the dead zone or temperature control is disabled. With a 2 pipe application, the control sequence state is determined by the application mode (see section 3.6.
3.6.3 2-pipe fan coil unit On 2-pipe applications, the thermostat controls a valve in heating / cooling mode with changeover (automatically or manually), heating only, or cooling only. Cooling only is factory-set (P01 = 1). ON/OFF control The diagrams below show the control sequence for 2-position control.
3.6.4 2-pipe fan coil unit with electric heater Heating or cooling with auxiliary heater On 2-pipe applications with electric heater, the thermostat controls a valve in heating / cooling mode with changeover, heating only, or cooling only plus an auxiliary electric heater. Cooling only is factory-set (P01 = 1) with enabled electric heater (P13). Electric heating, active in cooling mode In cooling mode, the valve receives an OPEN command if the acquired temperature is above the setpoint.
ON/OFF control The diagrams below show the control sequence for 2-position. Heating mode Cooling mode (automatic changeover = heating or heating only) (man. / auto.
3.6.5 4-pipe fan coil unit Heating and cooling On 4-pipe applications, the thermostat controls 2 valves in heating and cooling mode, heating / cooling mode by manual selection, or heating and cooling mode with changeover. Heating and cooling mode (P01 = 4) is factory-set. 4-pipe application with manual changeover The heating or cooling output can be released via operating mode button if parameter P01 is set to Manual (P01 = 2).
The diagrams below show the control sequence for 2-position control. Heating mode with manual selection (P01 = 2) Y 3076D01 Y Cooling mode with manual selection (P01 = 2) Y1 3076D13 ON/OFF control Y2 1 1 w 0 T[°C] ½ SDH w 0 ½ SDC ½ SDH T[°C] ½ SDC Heating and cooling mode (P01 = 04) Y1 ½ xdz Y2 ½ xdz 3076D11 Y 1 0 ½ SDH Notes: w ½ SDC ½ SDH T[°C] ½ SDC T[°C] Room temperature w Room temperature setpoint Y1 Control command “Valve” or “Comp.
3.6.6 Chilled / heated ceiling and radiator applications For chilled / heated ceiling and radiator, set the corresponding basic application disable the fan (P52) The following applications are available: Application for chilled / heated ceiling, radiator Chilled / heated ceiling with changeover Chilled / heated ceiling & el heater (cooling only: disable el heater via P13) Chilled ceiling and radiator 3.6.7 Set basic application 2-pipe See section 3.6.
3.6.8 Setpoints and sequences On changeover applications, the Comfort setpoints for heating and cooling sequence are the same (w). 2-pipe applications On 2-pipe applications with electric heater, the Comfort setpoint is either at the first heating sequence (in heating mode) or at the cooling sequence (in cooling mode). The setpoints for Economy and Protection mode are below the Comfort setpoints (heating) and above the Comfort setpoints (cooling).
On 4-pipe applications, the Comfort setpoint (w) is in the middle of the dead zone, between the heating and cooling sequence. 4-pipe applications The dead zone can be adjusted via parameter P33. If manual changeover is selected, then either the cooling sequence or the heating sequence is released. In this case, the Comfort setpoint is at the selected heating or cooling sequence.
Overview of control outputs 3.7 Control outputs 3.7.1 Overview Different control output signals are available. They need to be defined during commissioning (see below). Control output 2-position Product no. RDF301, RDF301.50, Y11, Y21 RDF600KN (2 x SPST) *) Only on 2-pipe application Note ON/OFF control signal (2-position) 2-position PWM 3-position DC 0…10 V --- Y11, Y21 *) (1 x / ) --- In the ACS tool, Y11 and Y21 are called Y1 and Y2.
3.7.2 Control outputs configuration (setting via DIP switches or tool) The type of the control outputs on 2-pipe applications (2- or 3-position) is set via DIP switches (see section 3.4). The DIP switches have no impact if the application is commissioned via tool. Control outputs need to be set via ACS in this case. Note In the tool, the parameter is called "Output Y1 / Y2", not Y11 / Y21). 40 / 82 Siemens Building Technologies RDF301, RDF301.
3.8 Fan control The fan operates in automatic mode or at the selected speed with manual mode. In automatic mode, the fan speed depends on the setpoint and the current room temperature. When the room temperature reaches the setpoint, the control valve closes and the fan switches off or stays at fan speed 1 (parameter P60). Factory setting for P60: RDF600KN fan Off in dead zone RDF301...
Look-up table with ON/OFF control SDH/SDC [K] XpHFan/XpCFan [K] 0.5 2 1.0 3 1.5 4 2.0 5 2.5 6 3.0 7 3.5 8 4.0 9 >4.5 10 1-speed / 3-speed fan The thermostat can control a 1- or 3-speed fan (selected via control parameter P53). A 1-speed fan is connected to terminal Q1, a 3-speed fan to terminals Q1, Q2 and Q3.
Fan overrun for electric heater Fan failure When the electric heater is switched off, the fan overruns for 60 seconds (parameter P54) to avoid overtemperature of the electric heater or prevent the thermal cutout from responding. In case of fan failure, the thermostat cannot protect the electric heater against overtemperature. For this reason, the electric heater must feature a separate safety device (thermal cutout).
3.9 Multifunctional input, digital input The thermostat has 2 multifunctional inputs X1 and X2 An NTC type sensor like the QAH11.1 (AI, analog input) or a switch (DI, digital input) can be connected to the input terminals. The functionality of the inputs can be configured via parameters P38 + P39 for X1 and P40 + P41 for X2. K NX The current temperature or state of the inputs X1/X2 is available on bus for monitoring purposes.
# 6 K NX Function of input Fault R Fault information K NX R 7 Monitor input (Digital) R 8 Monitor input (Temperature) X1, X2 (Digital) K NX X1, X2 (Temp.) Description Digital input to signal an external fault (example: dirty air filter). If the input is active, “ALx” is displayed and a fault is sent on the bus. See also section 3.11.8. (Alarm x, with x = 1 for X1, x = 2 for X2). Note: Fault displays have no impact on the thermostat's operation. They merely represent a visual signal.
3.11 KNX communications The RDF KNX thermostats support communications as per the KNX specification. S-mode Standard mode; engineering via group addresses. LTE mode Logical Tag Extended mode, for easy engineering, is used in conjunction with Synco. 3.11.1 S-mode This mode corresponds to KNX communications. Connections are established via ETS by assigning communication objects to group addresses. 3.11.2 LTE mode LTE mode was specifically designed to simplify engineering.
Engineering and commissioning For a detailed description of KNX (topology, bus supply, function and setting of LTE zones, filter tables, etc.), see "Communication via the KNX bus for Synco 700, 900 and RXB/RXL, Basic Documentation" [6] LTE mode data points and settings are described in the Synco Application Manual [12] To engineer and commission a specific system, use the Synco700 planning and commissioning protocol (XLS table in HIT, [7]) 3.11.
The zones to be defined are as follows: Geographical zone (space zone) Zone in which an RDF KNX thermostat is physically located. Other room-specific devices may also be located in this zone. (Apartment . Room . Subzone) Apartment = ---, 1...126 Room = ---, 1...63 Subzone = fix 1 Information exchanged in this zone is related specifically to the device like operating mode, setpoints, room temperature, etc. The designations "Apartment", "Room" and "Subzone" do not need to be taken literally.
3.11.4 Example of heating and cooling demand zone The building is equipped with Synco controls on the generation side and RDF / RDG thermostats on the room side. Konnex TP1 RMH760 Controller 1 RMB795 Controller 3 Controller 2 RDF... Controller 4 RDU... Controller 5 RDG...
3.11.5 Send heartbeat and receive timeout In a KNX network, S-mode and LTE mode communication objects can be exchanged between individual devices. The Receive timeout defines the period of time within which all the communication objects requested from a device must have been received at least once. If a communication object is not received within this period, a predefined value is used.
3.11.8 Fault function on KNX If a fault occurs (e.g. digital fault input, dew point, communication configuration, etc.) then a fault will be sent on the bus. An RDF thermostat listens on the bus and sends its fault when the fault has the highest alarm priority. This ensures that the management station does not miss any alarms. If alarms occur at the same time, the alarm with the highest priority will be first displayed and sent on the bus.
3.11.9 KNX switching groups (RDF301.50 only) K NX R Buttons ... Light and blinds as well as scenes are operated via switching groups. The communication objects of the buttons need to be bound to a corresponding KNX actuator module. 5 1 3 2 4 1, 2 Buttons of switching group left (1) 3, 4 Buttons of switching group right (2) 5 Display for indication while pressing buttons RDF301.50 has 2 switching groups with a pair of button each, which can be configured via ETS.
Parameters per switching group # Parameter Function left / right buttons Parameters per single button # Function Parameter 1 Switch “ON/OFF” functions 0 1 2 3 4 Parameter value Inactive (factory setting) Switch Dim Shutter Scene 0 Parameter value Child Parameter: Top: ON; bottom: OFF 1 Operating switching groups 2 “ON/OFF” functions Function top button: Toggle (ON/OFF) 0 ON 1 2 OFF Function bottom button: Toggle (ON/OFF) 0 ON 1 2 OFF # Function Parameter 4 Scene Scene number top button
3.12 Communication objects (S-mode) 3.12.
3.12.2 Description of communication objects Obj 1 Object name System time Function Type/ length Flags Time and 19.001 CWU date 8 Byte System time for display on the room thermostat. See parameter P07 (3 or 4) 3 Time of day Time and 10.001 CWU date 3 Byte Another object for receiving the time of day for display on the room thermostat. See parameter P07 (3 or 4) 4 Fault information Alarm 219.001 CT Info 6 Byte Common alarm output.
Obj 27 Object name Function Type/ length Flags Cooling output 0…100% 5.001 CRT 8 bit primary Indicates the position of the cooling actuator of the first stage. E.g. 2-pipe with electric heater application: Output of the cooling coil 29 Enable electric Enable / 1.003 CWU disable 1 bit heating An electric heater can be disabled with this communication object (e.g. to meet tariff regulations). The same function is also available via local multifunctional input X1/X2 (parameter P38, P40).
Obj 50 Object name Function Type/ length Flags Buttons left: Scene 18.001 CT control 8 bit Scene 56 Buttons right: Scene The “Scene (8-bit)” function is used to change the characteristics of a preset scene, i.e. brightness levels and switching states of a group within a scene, without using the ETS. For scene control, short and long (<1 s / > 3 s) pressing on the buttons are distinguished. On a short press, a telegram is sent to recall the corresponding scene.
3.13 Control parameters A number of control parameters can be readjusted to optimize control performance. This can be done on the thermostat via HMI or via commissioning / operating tool. These parameters can also be set during operation without opening the unit. In the event of a power failure, all control parameter settings are retained, see page 45.
3.13.2 Parameter setting / download via tool Control parameters can be adjusted via bus either by parameter download during commissioning or during normal operation with a tool like ACS.
Parameter 3.13.3 Parameters of the "Service level" Name Factory setting Range 2-pipe: 1 = Cooling only 0 = Heating only 1 = Cooling only 2 = H/C changeover manual 3 = H/C changeover auto 4 = Heating and Cooling 1 = Auto – Protection 2 = Auto - Comfort - Economy Protection C = ° Celsius F = ° Fahrenheit – 3 ... 3 K 0 = Room temperature 1 = Setpoint 0 = --- (No display) 1 = °C and °F 2 = Outside temperature (via bus) 3 = Time of day (12h) (via bus) 4 = Time of day (24h) (via bus) 5 ... 40 °C 5 ...
Parameter 3.13.4 Parameters of the "Expert level with diagnostics and test" Name Factory setting Range 0.5 … 6 K 0.5 … 6 K 0.5 … 5 K 0.5 … 5 K 0…10 min 0...120 min 10…25 °C 27…40 °C 0 = --- (no function) 1 = Room temp ext.
Parameter Name Factory setting Range 0…359 min, OFF(360) Off, 100…9900 h OFF, 5…WCoolProt; WCoolProt = 40 °C max OFF, WHeatProt… 40; WHeatProt = 5°C min 0...
4. Handling 4.1 Mounting and installation Mount the room thermostat on the conduit box. Do not mount on a wall in niches or bookshelves, behind curtains, above or near heat sources, or exposed to direct solar radiation. Mount about 1.5 m above the floor. Mounting / dismounting Mount the room thermostat in a clean, dry indoor place without direct airflow from a heating / cooling device, and not exposed to dripping or splash water RDF301...
4.2 Commissioning The room thermostats are delivered with a fixed set of applications. Applications Select and activate the relevant application during commissioning using one of the following tools: – Local DIP switch and HMI – Synco ACS – ETS Set the DIP switches before snapping the front panel to the mounting plate, if you want to select an application via DIP switches.
Control parameters The thermostat's control parameters can be set to ensure optimum performance of the entire system. The parameters can be adjusted using – Local HMI – Synco ACS – ETS Commissioning of switching groups for RDF301.50 is only possible with ETS). The control parameters of the thermostat can be set to ensure optimum performance of the entire system (see section 3.13, control parameters).
4.3 Operation See also Operating Instructions B3171 [2] enclosed with the thermostat. Layout 2 1 1 2 4 4 3 3 RDF301, RDF600KN RDF301.
Display 1 4 2 5 3 7 6 8 6 9 10 1 Operating mode Protection Comfort Economy Auto Timer according to schedule (via bus) 5 Condensation in room (dew point sensor active) 6 Indicates fault or reminder 7 Temporary Comfort mode extension active 2 Displays room temperature, setpoints and control parameters. Symbol indicates current room temperature 8 Additional user information, like or outside temperature time of day from KNX bus.
5. Supported KNX tools 5.1 ETS ETS is an engineering tool. It can be used for the full commissioning of the RDF KNX thermostats. ETS The following functions can be realized with ETS4: – – – – – Define and download the physical address Define and download the application (plant type, control sequence) Set up and download the thermostat's control parameters Download the switching group parameters (RDF301.
The application (plant type) and Control Sequence can be adjusted and downloaded. The control parameters, ([Pxx] description) can also be adjusted and downloaded. Refer to section 3.13. 5.2 ACS ACS Service and Operating tool With the ACS tool, the RDF KNX thermostats can be commissioned (physical address, application, parameters). They can be operated or monitored via bus during normal operation. This Manual does not describe how the physical address is defined.
5.2.1 Parameter settings in ACS In the ACS program, select Plant, then Open to open the plant. To start the parameter settings, select Applications, then Plant engineering…: The application and control parameters can be adjusted and downloaded. Column Line no. contains the parameter number as shown in the parameter table. Refer to section 3.13, control parameters. 70 / 82 Siemens Building Technologies RDF301, RDF301.
5.2.2 Operation and monitoring with ACS In the ACS program, select Plant, then Open to open the plant. To start monitoring and operation, select Applications, then Plant operation ACS Parameter settings in ACS Notes: ACS supports parameter settings even during normal operation. To change a control parameter, select Popcard, then Settings.
Plant diagram in ACS ACS offers plant diagrams for easy monitoring and operation of the thermostat. To start this application, select Applications, then Pant diagram 72 / 82 Siemens Building Technologies RDF301, RDF301.
ACS provides standard plant diagrams for RDF KNX thermostats, which depend on the configuration as follows: Plant type 2-pipe Application Configuration Application Configuration 2-pipe fan coil unit – Control sequence: No impact (P01 = any) – Fan operation: Not disabled (P52 <> 0) Radiator – Control sequence: Heating only (P01 = 0) – Fan operation: Disabled (P52 = 0) Chilled / heated ceiling – Control sequence: Changeover (P01 = 2,3) – Fan operation: Disabled (P52 = 0) Chilled ceiling – Control sequen
5.2.3 Operation and monitoring with OZW772 The OZW772 web server enables users to operate a Synco HVAC system from a remote location – via PC, or from a smart phone – using the HomeControl app. A start page shows the most important data points. A combination of menu / path navigation enables users to access all data points quickly and straightforwardly. The entire installation can be visualized in the form of plant diagrams.
Connection 6.1 Connection terminals L N SELV 3171A01 6. X1 M Q1 Q2 Q3 X2 CE+ CE Y11 N Y21 L, N Q1 Q2 Q3 Y11,Y21 X1, X2 M CE+ CE- Operating voltage AC 230 V Control output “Fan speed 1 AC 230 V” Control output “Fan speed 2 AC 230 V” Control output “Fan speed 3 AC 230 V” Control output “Valve” AC 230 V (NO, for normally closed valves), output for compressor or output for electric heater Multifunctional inputs for temperature sensor (e.g. QAH11.
Application Connection diagrams L AC 230 V F KNX S1 S2 B1 B2 L X1 M X2 CE+ CEY21 Y11 N Q1 Q2 Q3 Y1 M1 N 5(2)A max. 5(2)A max. Y1 5(2)A max. CE+ CEY1 5(2)A max. 4-pipe – Y1 = Heating – Y2 = Cooling 1-stage compressor – C1 = Heating and / or – C2 = Cooling) 1-stage compressor and electric heater N1 M1 Y1 Y1, Y2 E1 C1, C2 F S1, S2 B1, B2 2-pipe, 3-position – Y11 = Up – Y21 = Down 2-pipe and electric heater N1 10 A I II III 2-pipe, 2-position 3171A12 6.2 E1 5(2)A max.
7. Mechanical design 7.1 General The thermostats consist of 2 parts: Front panel with electronics, operating elements and built-in room temperature sensor Mounting base with power electronics The rear of the mounting base carries the screw terminals. Slide the front panel in the mounting base and snap on. 2 1 1 2 4 4 3 3 RDF301, RDF600KN RDF301.
7.2 Dimensions Dimensions in mm 86 16 30 80 3076M13_01 14 3076M12 3171M13 86 3076M01 3076M01 86 RDF600KN 86 RDF301... 78 / 82 Siemens Building Technologies RDF301, RDF301.
8. Power supply Outputs Inputs KNX bus Operational data Technical data Rated voltage Frequency Power consumption RDF301... RDF600KN Fan control Q1, Q2, Q3-N Rating Control output Y11-N / Y21-N (NO) Rating Max.
Environmental conditions Standards and directives Operation Climatic conditions Temperature Humidity Transport Climatic conditions Temperature Humidity Mechanical conditions Storage Climatic conditions Temperature Humidity conformity EMC directive Low-voltage directive C-tick conformity to EMC emission standard Reduction of hazardous substances Product standards Automatic electric controls for household and similar use Special requirements for temperature-dependent controls Electronic control type Genera
Index 1 1-speed fan........................................................... 42 3 3-position control signal........................................ 39 3-speed fan........................................................... 42 A Applications overview ........................................... 23 Auto Timer mode .................................................. 15 Automatic heating / cooling changeover ........ 25, 28 Automatic heating / cooling changeover via bus .. 25 B Basic application................
Reset parameters ................................................. 58 S Sensor input.......................................................... 44 Setpoint Comfort mode......................................... 37 Setpoint Economy mode....................................... 37 Setpoint limitation.................................................. 19 Setpoint Protection mode ..................................... 37 Setpoints and sequences ..................................... 37 Standby / Protection mode.......