Siemens RDF301, RDF301.50, RDF600KN Basic documentation CE1P3171en
Building Technologies Functions 2012-10-04
3.12 Communication objects (S-mode)
3.12.1 Overview
Page Object # and name Thermostat Object # and name Page
12 1 System time
12 3 Time of day
12 44 Outside temperature 21 Room temperature 12
16 Room operating mode:
State 1)
13
14 12 Room operating mode:
Time switch 1)
24 Room temperature:
Current setpoint
21
14 7 Room operating mode:
Preselection 1)
13, 15,
44
20
Room operating mode:
Window state
33 Fan operation
(0 = Auto / 1 = Manual)
41
35 Fan output 41
21 22 Room temperature:
Comfort basic setpoint
36 Fan stage 1 41
21 23 Room temperature:
Comfort setpoint
37 Fan stage 2 41
38 Fan stage 3 41
29 31 Application mode
25 Heating output primary 2) 50
41 32 Enable fan command value 26 Heating output secondary 2) 50
41 34 Fan command value 27 Cooling output primary 2) 50
32, 44 29 Enable electric heater
39/40 X1 (temperature / digital) 45
25, 44 30 Heating/cooling changeover 41/42 X2 (temperature / digital) 45
51 6 Fault transmission 5 Fault state 27, 51
4 Fault information 27, 43,
45, 51
45.. Buttons left: ON/OFF 52
45.. Button top left: ON/OFF 52
46.. Button bottom left: ON/OFF 52
47 Buttons left: Dim up/down 52
48 Buttons left: Blind step/stop 52
RDF301.50 49 Buttons left: Blind up/down 52
only 50 Buttons left: Scene 52
51.. Buttons right: ON/OFF 52
51.. Button top right: ON/OFF 52
53.. Button bottom right: ON/OFF 52
53 Buttons right: Dim up/down 52
54 Buttons right: Blind
step/stop
52
55 Buttons right: Blind up/down 52
56 Buttons right: Scene 52
Input communication object
Output communication object
Input & output communication object
1) 8-bit and 1-bit object available, selectable via parameter in ETS
2) Availability depending on selected application / function