Technical data

Modulating control: 3-position or PWM
The diagrams below show the control sequence of modulating PI control.
Heating mode with manual selection (P01 = 2)
Cooling mode with manual selection P01 = 2)
Y [%]
100
0
w
3181D1124b
T[°C]
XpH
YHYE
w
D
½ SDH ½ SDH
3181D105b
Y [%]
100
0
w
T[°C]
YC
XpC
Heating and cooling mode (P01 = 4)
Y [%]
100
0
w
3181D114b
T[°C]
YC
XpH
YH
XpC
½
x
dz
½
x
dz
YE
w
D
½ SDH
½ SDH
T[°C] Room temperature
w Room temperature setpoint
YE Control command "El heater"
(only On/Off)
YH Control command "Valve" (heating)
(On/Off or PWM, not 3-position)
YC Control command "Valve" (cooling)
(On/Off, PWM or 3-position)
XpH Proportional band "Heating" (P30)
XpC Proportional band "Cooling" (P31)
X
dz
Dead zone (P33)
w
D
Setpoint differential (P34)
The diagrams only show the PI thermostats proportional part.
Setting the sequence and the control outputs
Refer to sections 3.4 "Applications", 3.6.1 "Sequences", and 3.7 "Outputs".
YH can only be On/Off or PWM
YC can be On/Off, PWM or 3-position
YE can only be On/Off