Technical data

3.6.9 Chilled / heated ceiling and radiator applications
For chilled / heated ceiling and radiator,
set the corresponding basic application according to section 3.4
disable the fan (P52)
The following applications are available:
Application for
chilled / heated ceiling, radiator
Set basic application
See
section
Sequences
Chilled / heated ceiling with
changeover
2-pipe 3.6.3
H ( \ )
C ( / )
Chilled / heated ceiling & el heater
(cooling only: disable el
heater via P13)
2-pipe and electric heater 3.6.4
El H + H ( \ \ )
El H + C (
\ / )
C ( / )
Chilled / heated ceiling and
radiator
2-pipe and radiator
3.6.5
H + rad ( \ r\ )
Rad + C ( r\ / )
Chilled ceiling and radiator
4-pipe 3.6.6
H + C ( \ / )
Chilled / heated ceiling, 2-stage
2-stage heating or cooling
3.6.8
H + H ( \ \ )
C + C ( / / )
3.6.10 Compressor applications (RDG160KN)
For compressor applications,
set the corresponding basic application according to section 3.4
disable the fan (P52) or set the type of fan speed (P53)
Select the type of control outputs (On/Off or DC 0...10 V, P46, P47)
The following applications are available:
Minimum on/off time: P48 / P49 (only with On/Off control outputs)
Fan operation: P52 (0 = disabled, 1 = enabled)
Fan speed: P53 (1 = 1-speed, 2 = 3-speed, 3 = DC 0...10 V)
Control outputs DC 0...10 V: P46 = 2 (V1) P47 = 2 (V2)
Control outputs 2-position: P46 = 1 (V1) P47 = 1 (V2) (only with EC (DC) fan
Application for
compressors in DX-type
equipment
Set basic application
See section
Sequences
1-stage compressor
2-pipe 3.6.3
H ( \ )
C ( / )
1-stage compressor and el.
heater
(cooling only: disable
el. heater via P13)
2-pipe and electric heater
3.6.4
El. H + H ( \ \ )
El. H + C (
\ / )
C ( / )
1-stage compressor
for heating and cooling
4-pipe 3.6.6
H + C ( \ / )
2-stage compressor
2-stage heating or cooling
3.6.8
H + H ( \ \ )
C + C ( / / )
Notes
46 / 102
Siemens RDG100KN, RDG160KN Basic documentation CE1P3191en
Building Technologies Functions 2014-05-23