Technical data
• For a detailed description of KNX (topology, bus supply, function and setting of
LTE zones, filter tables, etc.), see "Communication via the KNX bus for Synco
700, 900 and RXB/RXL, Basic Documentation" [6].
• LTE mode data points and settings are described in the Synco Application
Manual [12].
• To engineer and commission a specific system, use the Synco700 planning and
commissioning protocol (XLS table in HIT, [7]).
3.11.3 Zone addressing in LTE mode (in conjunction with
Synco)
In cases where RDG KNX room thermostats are used in LTE mode (e.g. in
conjunction with Synco), zone addresses need to be allocated.
The following zone address must be defined together with the Synco devices at the
planning stage depending on the application.
Short description
Factory setting
Parameter
Geographical zone (apartment)
--- (out of service)
P82
Geographical zone (room)
1
P83
Heat distr zone heating coil
1
P84
Refr distr zone cooling coil
1
P85
Heat distr zone heating surface
2
P86
Note: "Subzone" of "Geographical zone" is fix 1 (not adjustable)
The device will send and receive LTE communication signals only if the zone
address is valid (not OSV = out of service).
RDG
Chiller
Sensor
Outside temperature zone 31
Refr. distr zone 1
Geogr. zone 2.5.1
Heat distr zone 1
Cool demand
Outside temperature
Outside temperature
Cool demand
Outside temperature zone 31
Refr. distr zone 1
Heat demand
Time Switch
Operating mode Operating mode
Boiler
Heat distr zone 1
Heat demand
Geogr. zone 2.5.1 or 2.1.1
Room temperature
Engineering and
commissioning
61 / 102
Siemens RDG100KN, RDG160KN Basic documentation CE1P3191en
Building Technologies Functions 2014-05-23