Technical data
3.14 Control parameters
A number of control parameters can be readjusted to optimize control performance.
This can be done on the thermostat via HMI or via commissioning / operating tool.
These parameters can also be set during operation without opening the unit.
In the event of a power failure, all control parameter settings are retained.
The control parameters are assigned to 2 levels:
• "Service level", and
• "Expert level" including communications, diagnostics and test
The "Service level" contains a small set of parameters to set up the thermostat for
the HVAC system and to adjust the user interface. These parameters can be
adjusted any time.
Change parameters at the "Expert level" carefully, as they impact the thermostat’s
control performance and functionality.
3.14.1 Parameter setting via local HMI
1. Press left and right button simultaneously for 4 seconds.
Release and press the right button again within 2 seconds until the display
shows "P01".
Continue with step 2.
1. Press left button and right button simultaneously for 4 seconds.
Release and press the left button again within 2 seconds until the temperature
disappears.
Turn the rotary knob counterclockwise min. ½ rotation.
The display shows "Pxx".
Continue with step 2.
2. Select the required parameter by turning the rotary knob.
3. Press button (OK); the current value of the selected parameter starts
blinking and can be changed by turning the rotary knob.
4. Press button (OK) to confirm the adjusted value or press button (Esc)
to cancel the change.
5. If you wish to adjust additional parameters, repeat steps 2…4.
6. Press button (Esc) to leave the parameter setting mode.
The factory setting for the control parameters can be reloaded via parameter P71,
by changing the value to "ON". Confirm by pressing the right button.
The display shows "8888" during reloading.
Enter only "Service
level"
Enter "Expert level"
and "Diagnostics
&
test"
Adjust parameters
Reset parameters
70 / 102
Siemens RDG100KN, RDG160KN Basic documentation CE1P3191en
Building Technologies Functions 2014-05-23