Technical data

3.14.4 Parameters of the "Expert level
with diagnostics and test"
Parameter
Name
Factory setting
Range
RDG100KN
RDG160KN
Dependen-
cies
Expert level
P30
Heat P-band Xp / switching diff
2 K
0.5 … 6 K
P31
Cool P-band Xp / switching diff
1 K
0.5 … 6 K
P32
Radiator P-band Xp / swi diff
2 K
0.5 … 6 K
Appl
P33
Dead zone Comfort mode
2 K
0.5 … 5 K
Appl
P34
Setpoint differential
2 K
0.5 … 5 K
Appl
P35
Integral action time Tn, RDG100KN
5 min
0…10 min
x
P46, P47
RDG160KN
45 min
0...120 min
x
P46, P47
P36
H/C ch'over swi point cooling
16 °C
10…25 °C
P38, P40
P37
H/C ch'over swi point heating
28 °C
27…40 °C
P38, P40
P38 Input X1
RDG100KN (range 0..8)
RDG160KN (range 0..9)
1: = Ext. sensor
0 = --- (no function)
1 = Room temp ext. sensor /
Return air temp (AI)
2 = H/C changeover (AI/DI)
3 = Operating mode contact (DI)
4 = Dew point sensor (DI)
5 = Enable electric heater (DI)
6 = Fault input (DI)
7 = Monitor input (Digital)
8 = Monitor input (Temp)
9 = Supply air sensor
P39
Normal position input X1
0 (N.O.)
0 = Normally open / Open
1 = Normally closed / Close
P38
P40
Input X2
RDG100KN (range 0..8)
RDG160KN (range 0..9)
0 = no function
0 = --- (no function)
1 = Room temp ext. sensor /
Return air temp (AI)
2 = H/C changeover (AI/DI)
3 = Operating mode contact (DI)
4 = Dew point sensor (DI)
5 = Enable electric heater (DI)
6 = Fault input (DI)
7 = Monitor input (Digital)
8 = Monitor input (Temp)
9 = Supply air sensor
P41
Normal position input X2
0 (N.O.)
0 = Normally open / Open
1 = Normally closed / Close
P40
P42 Input D1 3 = Op mode contact
0 = --- (no function)
2 = H/C changeover (DI)
3 = Operating mode contact (DI)
4 = Dew point sensor (DI)
5 = Enable electric heater (DI)
6 = Fault input (DI)
7 = Monitor input (Digital)
P43 Normal position input D1 0 (N.O.)
0 = Normally open / Open
1 = Normally closed / Close
P42
P44
Actuator running time Y1/Y2
150 s
20…300 sec
x
P46
P45
Actuator running time Y3/Y4
150 s
20…300 sec
x
P47
P45
Power of electric heater on Q2 (for
adaptive temperature compensation)
0 kW
0.0 ….. 1.2 kW
x
P46
Output Y1/Y2
On/Off (1)
0 = 3-position
1 = On/Off
2 = PWM
x
Appl
P46
Outputs Y10 (DC) or Q1 (2-pos)
2 = DC 0...10 V
1 = On/Off
2 = DC 0...10 V
x
Appl
P47
Output Y3/Y4
On/Off (1)
0 = 3-position
1 = On/Off
2 = PWM
x
Appl
P47
Outputs Y20 (DC) or Q2 (2.pos)
2 = DC 0...10 V
1 = On/Off
2 = DC 0...10 V
x
Appl
P48
On time minimum 2-pos output
1 min.
1...20 min
P46
73 / 102
Siemens RDG100KN, RDG160KN Basic documentation CE1P3191en
Building Technologies Functions 2014-05-23