Technical data

Parameter
Name
Factory setting
Range
RDG100KN
RDG160KN
Dependen-
cies
Expert level
P49
Off time minimum 2-pos output
1 min.
1...20 min
P47
P50
Purge time
OFF
OFF: Not active
1…5 min: Active with selected
duration
P38, P40
P51
Flow temp limit floor heating
OFF
OFF, 10...50 °C
P38, P40
P52 Fan control 1 = Enabled
0 = Disabled
1 = Enabled
2 = Heating only
3 = Cooling only
P53
Fan speeds RDG100KN
2 = 3-speed
1 = 1-speed
2 = 3-speed
x
P52
P53
Fan speeds RDG160KN
3 = DC 0...10 V
1 = 1-speed fan
2 = 3-speed fan
3 = DC 0...10 V (ECM fan)
x
P52
P54
Fan overrun time
60 sec
0...360 sec
P52, Appl
P55 Fan speed switching point high 100% 80...100%
P52, P53, DIP
ECM fan max. output
ECM: 80%
ECM: fan min…100%
x
P52, P53, DIP
P56
Fan speed switching point med
65%
30..75%
P52, P53, DIP
ECM fan min. output
ECM: 30%
ECM: 1%...fan max.
x
P52, P53, DIP
P57
Fan speed switching point low
10%
1...15%
P52, P53, DIP
ECM: Switching point fan
ECM:10%
ECM: 1..100%
x
P52, P53, DIP
P58
Fan start kick
ON
ON: Enabled
OFF: Disabled
P52
P59 On time minimum fan 2 min 1...6 min
P52
P60 Periodic fan kick Comfort
RDG100KN
RDG160KN
0
OFF
0…89 min, OFF
P52
P61
Periodic fan kick Eco
OFF
0…359 min, OFF
P52
P62
Service filter
OFF
Off, 100…9900 h
P52
P63 Minimum supply air temperature OFF OFF, 0…P64 °C x
P38, P40
P64
Maximum supply air temperature
OFF
OFF, P63 … 50°C
x
P38, P40
P65
Protection heating setpoint
8 °C
OFF, 5…WCoolProt;
WCoolProt = 40 °C max
P66
Protection cooling setpoint
OFF
OFF, WHeatProt… 40;
WHeatProt = 5°C min
P67
Fan start delay RDG100KN
RDG160KN
0 s
0...180 s
0...360 s
P52, P46, P47
P68
Temporary Comfort mode
0 (= OFF)
0...360 min
P02
P69 Temporary Comfort setpoint OFF
OFF = Disabled
ON = Enabled
P71 Restore factory setting OFF
OFF = Disabled
ON = Reload start
"8888" is displayed for 3s during
reload process
P74 Output Q3 function 0 0 = No function
1= Switch OFF in Protection
x
P45: To compensate for heat dissipation of the el. heater relay in RDG160KN.
P46, P47: Setting to 2-position or 3-position is made with DIP switches 4 and 5.
Note:
74 / 102
Siemens RDG100KN, RDG160KN Basic documentation CE1P3191en
Building Technologies Functions 2014-05-23