Technical data
Parameter
Name
Factory setting
Range
Dependencies
Communications
P81
Device address 1)
255
1…255
P82
Geographical zone (apartment) 2)
---
---, 1...126
P83 Geographical zone (room) 2) 1 ---, 1...63
P84
Heat distr zone heating coil
---
---, 1...31
Appl, P01
P85
Refrig distr zone cooling coil
---
---, 1...31
Appl, P01
P86 Heat distr zone heating surface --- ---, 1...31 Appl
P88
Transformation Precomfort
0
0 = Economy
1 = Comfort
1) Physical address = Area.Line.DeviceAddress. Factory setting of Area = 0, Line = 2.
Can be changed by special management service e.g. from line coupler or via ACS commissioning tool.
2) Type = geographical zone A.R.S. In RDG sub zone = fixed value 1.
Parameter
Name
Range
Dependen-
cies
Diagnostics & test
d01
Application number
0 = (No application)
1 = 2-pipe
2 = 2-pipe with electric heater
3 = 2-pipe with radiator
4 = 4-pipe
5 = 2-stage heating or cooling
6 = 4-pipe with electric heater
d02
X1 state
"---" = function not selected
0 = Not activated (for DI)
1 = Activated (DI)
0…49 °C = Current temp. value (for AI)
00
= H/C Input shorted
100 = H/C Input open
d03
X2 state
"---" = function not selected
0 = Not activated (for DI)
1 = Activated (DI)
0…49 °C = Current temp. value (for AI)
00
= H/C Input shorted
100
= H/C Input open
d04 D1 state
"---" = function not selected
0 = Not activated (for DI)
1 = Activated (DI)
00
= H/C Input shorted
100
= H/C Input open
d05
Test mode for checking the Y1/Y2 actuator's running
direction 3)
"---" = no signal on outputs Y1 and Y2
OPE = output Y1 forced opening
CLO = output Y2 forced closing
P46
d06
Test mode for checking the Y3/Y4 actuator's running
direction 3)
"---" = no signal on outputs Y3 and Y4
OPE = output Y3 forced opening
CLO = output Y4 forced closing
P47
d07
Software version
Ux.xx is displayed
d10
Test mode for checking the Q3 output (P74 function)
(RDG160KN)
"---" = no signal at output Q3
OPE = output Q3 forced opening
CLO = output Q3 forced closing
P74, App
3) This parameter can only be quit when the setting is back at "---".
Press the left button to escape.
75 / 102
Siemens RDG100KN, RDG160KN Basic documentation CE1P3191en
Building Technologies Functions 2014-05-23