Technical data

Operating modes: Comfort, Economy and Protection
Automatic or manual heating / cooling changeover
Backlit display
RDG100KN:
On/Off, PWM or 3-position control outputs (triac)
Output for 3-speed or 1-speed fan
AC 230 V operating voltage
RDG160KN:
DC 0...10 V or On/Off control outputs for actuators
DC 0...10 V or relay outputs for fan (ECM or 1 / 3 speed)
AC 24 V operating voltage
Room temperature control via built-in temperature sensor or external room
temperature / return air temperature sensor
Changeover between heating and cooling mode (automatic via local sensor or
bus, or manually)
Selection of applications via DIP switches or commissioning tool (ACS, ETS).
Parameters download with commissioning too (ACS, ETS)
Select operating mode via operating mode button on the thermostat
Temporary Comfort mode extension
1- or 3-speed, or DC 0...10 V fan control (automatically or manually)
Display of current room temperature or setpoint in °C and/or °F
Minimum and maximum limitation of room temperature setpoint
Button lock (automatically or manually)
3 multifunctional inputs, freely selectable for:
Operating mode switchover contact (keycard, window contact, etc.)
Sensor for automatic heating / cooling changeover
External room temperature or return air temperature sensor
Dew point sensor
Electric heater enable
Fault input
Monitor input for temperature sensor or switch state
Supply air temperature sensor (RDG160KN)
Advanced fan control function, e.g. fan kick, fan start delay, selectable fan
operation (enable, disable or depending on heating or cooling mode)
"Purge" function together with 2-port valve in a 2-pipe changeover system
Reminder to clean fan filters (adjustable with P62)
Floor heating temperature limitation
Minimum and maximum supply air temperature limitation (RDG160KN)
Reload factory settings for commissioning and control parameters
KNX bus (terminals CE+ and CE-) for communication with Synco or KNX
compatible devices
Display of outside temperature or time of day via KNX bus
Time scheduling and central control of setpoints via KNX bus
With a Synco RMB795 controller, the energy demand signal of the thermostat is
used to optimize energy supply
Selectable relay function for switching external equipment (RDG160KN)
Features
Functions
8 / 102
Siemens RDG100KN, RDG160KN Basic documentation CE1P3191en
Building Technologies Summary 2014-05-23