Technical data

Plant type
Application
Configuration
Application
Configuration
2-pipe and
electric
heater
2-pipe fan coil unit with electric heater
Control sequence: No impact (P01 = any)
Fan operation: Not disabled (P52 <> 0)
Single stage with electric heater
Control sequence: No impact (P01 =any)
Fan operation: Disabled (P52 = 0)
2-pipe and
radiator
2-pipe fan coil unit with radiator
Control sequence: No impact (P01 = any)
Fan operation: Not disabled (P52 <> 0)
Single stage with radiator
Control sequence: No impact (P01 =any)
Fan operation: Disabled (P52 = 0)
4-pipe
4-pipe fan coil unit
Control sequence: Not auto c/o (P01 <> 3)
Fan operation: Not disabled (P52 <> 0)
Chilled ceiling with radiator
Control sequence: No impact (P01 =any)
Fan operation: Disabled (P52 = 0)
Fan coil unit main / secondary
Control sequence: Auto c/o (P01 = 3)
Fan operation: Not disabled (P52 <> 0)
Main / secondary
Control sequence: Auto c/o (P01 = 3)
Fan operation: Disabled (P52 = 0)
2-stage
heating or
cooling
2-stage fan coil unit
Control sequence: No impact (P01 = any)
Fan operation: Not disabled (P52 <> 0)
2-stage
Control sequence: No impact (P01 =any)
Fan operation: Disabled (P52 = 0)
87 / 102
Siemens RDG100KN, RDG160KN Basic documentation CE1P3191en
Building Technologies Supported KNX tools 2014-05-23