Technical data
6. Connection
6.1 Connection terminals
RDG100KN
L X1 M
N
Q1 Q2 Q3
Y1
SELV
X2
3191A01
CE+ CE
-
D1 GND
Y2 Y3 Y4
RDG160KN
L
G X1 M
G0
Q1 Q2 Q3
Y50
SELV
X2
3191A11
CE+ CE
-
D1 GND
Y10 Y20
L, N Operating voltage AC 230 V (RDG100KN)
G, G0 Operating voltage AC 24 V (RDG160KN)
L Feed for relays AC 24...230 V (RDG160KN)
X1, X2 Multifunctional input for temperature sensor
(e.g. QAH11.1) or potential-free switch
Factory setting:
– X1 = External temperature sensor
– X2 = No function
(function can be selected via parameters P38 / P40).
M Measuring neutral for sensors and switches
D1, GND Multifunctional input for potential-free switch
Factory setting: Operating mode switchover contact
(function can be selected via parameter P42).
Q1 Control output fan speed "low" AC 230 V
Q2 Control output fan speed "medium" AC 230 V
Q3 Control output fan speed "high" AC 230 V
Q1...Q3 Also for special functions AC 24...230 V (RDG160KN)
Y1…Y4 Control outputs "Valve" AC 230 V (RDG100KN)
("N/O" triac, for normally closed valves),
output for electric heater via external relay
Y10, Y20 Control outputs "Valve" DC 0...10 V (RDG160KN)
Y50 Control output "Fan" DC 0...10 V (RDG160KN)
CE+ KNX data +
CE- KNX data –
90 / 102
Siemens RDG100KN, RDG160KN Basic documentation CE1P3191en
Building Technologies Connection 2014-05-23