Smart Thermostat Wireless RDS110.R To control heating applications in apartments, single family homes, dormitories, and other residential as well as commercial spaces.
Room thermostat features ● ● ● Direct temperature and operating mode selection RoomOptiControl1) function with Green leaf indication for energy-optimized operation Temperature setting limitation for use in public spaces ● Air quality indication: Good ● ● ● Screen lock protection against unauthorized access Manual switchover between At home, Away and Off on touch screen Room temperature detection and control using the built-in temperature sensor or an optional remote sensor Optional temperature averagin
RDS110.R with radiator valve actuator (SSA911.01TH): ● Radiator with valve (SSA911.01TH) Note: The RDS110.R can control max. 6 valve actuators in parallel, i.e. with the same control settings. RDS110.R with wireless receiver (RCR114.
Topology Notes: 1. Install the receiver close to RDS110.R if possible. The communication range in a building is typically 60 m, without any blockades. Please note the range can vary, as walls, floors, wireless interference and other factors may reduce the signal strength. 2. Add a repeater (RCR114.1) if the connection fails due to low signal strength (distance or blockades (walls, etc.)). 3.
Operation and settings Normal display 1 Tap to display detailed information and additional settings. 2 Tap to display additional measurements, for example, outside air temperature. (Only if external sensor is connected) 3 Tap to display notifications (only visible if any) 4 Room temperature 5 Tap to toggle between At home and AWAY. 6 Displays whether the thermostat is following a schedule ( setpoint changes permanently ( ● ● ● 7 ) or following your ).
NOTICE After initial setup of the thermostat, the displayed room temperature may not be correct because the temperature sensors need time for calibration. Wait for at least one hour for the calibration. Idle display The RDS110.R screen switches to idle mode after 2 minutes of inactivity. The idle screen of the RDS110.R can be displayed as a simple screen with basic room values, or as a blank, black screen. The simple screen is the default setting.
Ordering ● ● When ordering, indicate product number, stock number and description. Order valve actuators separately. Inbox items Items Quantity Thermostat (front and rear) 1 Metallic mounting plate 1 Set of screws and plastic insert 1 Quick guide 1 Mounting instructions 1 Activation code sticker 1 Wiring sticker 1 Equipment combinations Receiver Type of unit Product number Stock number Datasheet* Smart Thermostat Receiver RCR114.
Type of unit Product no. LGNi1000 at 0 °C QAC2012 Pt1000 at 0 °C NTC 10k DC 0…10 V Datasheet* at 25 °C x QAC2030 CE1N1811 x QAC3161 CE1N1811 x CE1N1814 Cable temperature sensors QAP21.3 x CE1N1832 QAP22 x CE1N1831 QAP21.3/800 0 x CE1N1832 QAP2012.150 x QAP1030.200 CE1N1831 x CE1N1831 Room humidity sensors - Wall-mounted QFA2000 x CE1N1857 - Wall-mounted including temperature QFA2020 x (r.h.) CE1N1857 QFA2060 x (T+r.h.) CE1N1857 QFA2060D2) x (T+r.h.
* The documents can be downloaded from http://siemens.com/bt/download by specifying the product number as shown in the above table. 1) Requires a mounting plate and/or design frames. 2) With digital display. Accessories (Optional) Type of unit Product no. Datasheet* White decorative frame and metallic mounting plate for installation on rectangular conduit box (1 set) ARG100.01 S55772-T102 A6V11190640 Note: Accessories are not included with the units and should be ordered separately.
WARNING No internal line protection for supply lines to external consumers Risk of fire and injury due to short-circuits ● ● ● ● ● Adapt the line diameters as per local regulations to the rated value of the installed overcurrent protection device. The AC 230 V mains supply line must have an external circuit breaker with a rated current of no more than 10 A. Use only AC 230 V isolated wired cables, as the conduit box carries AC 230 V mains voltage. Inputs X1-M-X2: Several switches (e.g.
Operation End users can operate the thermostat directly on the touch screen, or download the mobile app Siemens Smart Thermostat RDSand perform operations on their smartphones, including: ● Creating and managing accounts ● Setting the operating mode (Auto, away, home, manual) ● Changing the room temperature (by setting new setpoints) ● Setting a weekly schedule (heating and domestic hot water) ● Opting for geo-fencing ● Selecting the Green leaf (switching to energy-optimized operation) ● Viewing temperature
Technical data Power supply Power supply Operating voltage AC 230 V (+10% / -15%) Frequency 48…63 Hz Power consumption Max. 9 VA Standby power consumption (LCD off) 1.6 W Max. external supply line fusing 10 A circuit breaker Radio parameters Radio parameters 12 Smart Infrastructure Frequency band 2.4…2.4835 GHz Maximum radio-frequency power 18 dBm WLAN standard IEEE 802.11b/g/n (HT20) WLAN channel 1~13 Frequency band Maximum radio-frequency power Thread standard Thread channel 2.4…2.
Inputs Connections to multifunctional inputs X1 - M - X2 Passive temperature sensors - Cable length max. (copper cable section) 90 m (1.5 mm2 wire), 70 m (1 mm2 wire) 60 m (0.75 mm2 wire), 40 m (0.
Connections Interfaces Micro USB A service port is limited to firmware upgrades and onsite diagnosis by professionals. Wiring connections Screw terminal Solid wires or prepared stranded wires: Max. 1 × 0.5... 2.
Eco design and labeling directives Based on EU Regulation 813/2013 (Eco design directive) and 811/2013 (Labelling directive) concerning space heaters, combination heaters, the following classes apply: Application with On/Off operation of a heater Class I Value 1% PWM (TPI) room thermostat, for use with On/Off output heaters Value 2% Class IV General data General Dimension Refer to Dimensions on page 18 Weight Thermostat with package, user document and accessory 534 g Thermostat 219 g Color Silv
Wiring diagrams 16 Smart Infrastructure L, N Operating voltage AC 230 V B1, B2 External sensors X1, X2, M Multifunctional inputs S1, S2 External switches A6V11562461_en--_a 2019-09-19
Application examples Applications Smart Infrastructure Gas boiler (with RCR114.1) Electric boiler (with RCR114.1) Radiator with valve (with SSA911.01.TH) Floor heating with valve (with RCR114.1) Radiator with pump (with RCR114.1) Floor heating with pump (with RCR114.1) Electric radiator (with RCR114.1) Electric floor heating (with RCR114.
Applications Fan with electric heating Domestic hot water boiler (with RCR114.1) (with RCR114.1) N1 N2 F1, F2 K1 Y1 Y2 Y3 Y4 M1 RDS110.R RCR114.1 Limit thermostats Heat generator (e.g. boiler) Magnetic valve Domestic hot water boiler Valve SSA911.01TH Circulating pump Dimensions RDS110.
ARG100.01 White decoration frame Metallic mounting plate Revision history Smart Infrastructure Edition Date Software version Changes Section Pages 1 September 2019 45.4.
Issued by Siemens Switzerland Ltd Smart Infrastructure Global Headquarters Theilerstrasse 1a CH-6300 Zug Tel. +41 58 724 2424 www.siemens.com/buildingtechnologies 20 Smart Infrastructure Document ID A6V11562461_en--_a Edition 2019-09-19 © Siemens Switzerland Ltd, 2019 Technical specifications and availability subject to change without notice.