User Manual

10
Smart Infrastructure
A6V11562461_en--_a
2019-09-19
WARNING
No internal line protection for supply lines to external consumers
Risk of fire and injury due to short-circuits
Adapt the line diameters as per local regulations to the rated value of the installed
overcurrent protection device.
The AC 230 V mains supply line must have an external circuit breaker with a rated
current of no more than 10 A.
Use only AC 230 V isolated wired cables, as the conduit box carries AC 230 V mains
voltage.
Inputs X1-M-X2: Several switches (e.g. window contact) may be connected in parallel.
Consider overall maximum contact sensing current for switch rating.
Disconnect from power supply before removing the front of the thermostat.
Commissioning
Refer to the Quick guide and User guide (see Product Documentation) to configure your
device. Commissioning includes the following:
Internet connection
Application setup
Account registration and device pairing
Note:
Before configuring your thermostat, make sure you are connected to the Internet, have a
valid email address, and a smartphone.
Mounting
The devices are suitable for wall mounting.
Recommended height: 1.50 m above the floor.
Do not mount the devices in recesses, shelves, behind curtains or doors, or above or
near heat sources.
Avoid direct solar radiation.
Seal the conduit box or the installation tube if any, as air currents can affect sensor
readings.
Adhere to allowed ambient conditions.