User Manual

Operating the thermostat on the device
Advanced settings
28
| 60
A6V11562455_en--_a
No.
Application
settings
Descriptions
Factory
settings
Range
Dependencies
1. Room
temperature
1, 0 V value
Room temperature at
0 V of the 0-10 V
input in terminal X1
0 °C 0…50 °C
A DC 0…10 V
external room
temperature
sensor must be
connected to
the thermostat
using terminal
X1.
2. Room
temperature
1, 10 V
value
Room temperature at
10 V of the 0-10 V
input in terminal X1
50 °C 0…50 °C
3.
Room
temperature
2, 0 V value
Room temperature at
0 V of the 0-10 V
input in terminal X2
0 °C 0…50 °C
A DC 0…10 V
external room
temperature
sensor must be
connected to
the thermostat
using terminal
X2.
4. Room
temperature
2, 10 V
value
Room temperature at
10 V of the 0-10 V
input in terminal X2
50 °C 0…50 °C
5.
Outside air
temperature,
0 V value
Outside air
temperature at 0 V of
the 0-10 V input
-50 °C -50…80 °C
A DC 0…10 V
external
outside air
temperature
sensor must be
connected.
6. Outside air
temperature,
10 V value
Outside air
temperature at 10 V
of the 0-10 V input
80 °C -50…80 °C
7.
Floor
temperature
1, 0 V value
Floor temperature at
0 V of the 0-10 V
input in terminal X1
-50 °C -50…80 °C
A DC 0…10 V
external floor
temperature
sensor must be
connected
using terminal
X1.
8. Floor
temperature
1, 10 V
value
Floor temperature at
10 V of the 0-10 V
input in terminal X1
80 °C -50…80 °C
9. Floor
temperature
2, 0 V value
Floor temperature at
0 V of the 0-10 V
input in terminal X2
-50 °C -50…80 °C
A DC 0…10 V
external floor
temperature
sensor must be
connected
using terminal
X2.
10.
Floor
temperature
2, 10 V
value
Floor temperature at
10 V of the 0-10 V
input in terminal X2
80 °C -50…80 °C
Multi-functional inputs