User Manual
Operating the thermostat on the device
Advanced settings
6
30
| 60
A6V11562455_en--_a
No.
Application
settings
Descriptions
Factory
settings
Range
Dependencies
16. Rel.room
humidity
setpoint for
comfort
The humidification
setpoint for
Comfort
. This
setpoint must be
higher than the
humidification
setpoint for
protection.
40 % RH 0…100 % RH Displays only
if you’ve
configured the
output as
Humidifier (no
fan)
.
17.
Rel.room
humidity
setpoint for
economy
The humidification
setpoint for
Economy
. This
setpoint must be
higher than the
humidification
setpoint for
protection.
40 % RH 0…100 % RH
18.
Rel.room
humidity
setpoint
f.unoccupied
The humidification
setpoint for
Unoccupied
. This
setpoint must be
higher than the
humidification
setpoint for
protection.
30 % RH 0…100 % RH
19. Rel.room
humidity
setp.for
protection
The humidification
setpoint to maintain
when you switch the
thermostat to
OFF
under >
Operating mode
.
This setpoint must
be lower than the
dehumidification
setpoint for
protection.
30 % RH 0…100 % RH This setting
displays only if
you’ve
configured the
output as
Humidifier (no
fan)
.
This setpoint
is valid only if
you keep the
default
Protection
option for
Application
setting No. 35.
NOTE: Humidification control works with a PID algorithm. The algorithm
continuously monitors the difference between the humidity setpoint for
humidification and the measured relative air humidity in the room and switches the
humidifier ON and OFF to keep the humidity above the setpoint. The humidifier
cannot manually be switched on and off. Changes to the setpoint impact
humidification control, thereby verifying functionality.
Humidification setpoints