User Manual
Operating the thermostat on the device
Advanced settings
6
A6V11562455_en
--_a
33 | 60
No.
Application
settings
Descriptions
Factory
settings
Range
Dependencies
29. Humidify
(no fan)
min. ON
time
The minimum working
time of a standalone
humidifier. This
minimum limitation
protects the humidifier
from being destroyed
by frequent
switchovers.
3 min 0…60 min
You’ve
configured the
thermostat
output as
Humidifier (no
fan)
in
Changing
system setup
[➙ 35].
30.
Humidify
(no fan)
min. OFF
time
The minimum OFF
time of a standalone
humidifier. This
minimum limitation
protects the humidifier
from being destroyed
by frequent
switchovers.
3 min 0…60 min
31.
Dehum. (no
fan) min.
ON time
The minimum working
time of a standalone
dehumidifier. This
minimum limitation
protects the
dehumidifier from
being destroyed by
frequent switchovers.
3 min 0…60 min
You’ve
configured the
thermostat
output as
Dehumidifier
(no fan)
in
Changing
system setup
[➙ 35].
32. Dehum. (no
fan) min.
OFF time
The minimum OFF
time of a standalone
dehumidifier. This
minimum limitation
protects the
dehumidifier from
being destroyed by
frequent switchovers.
3 min 0…60 min
33. DHW min.
ON time
The minimum working
time of the domestic
hot water boiler. This
minimum limitation
protects the boiler
from being destroyed
by frequent
switchovers.
3 min 0…60 min
You’ve
configured the
thermostat
output as
Hot
water
in
Changing
system setup
[➙ 35].
34. DHW min.
OFF time
The minimum OFF
time of the domestic
hot water boiler. This
minimum limitation
protects the boiler
from being destroyed
by frequent
switchovers.
3 min 0…60 min
Minimum switchover time
adjustment