User Manual
Operating the thermostat on the device
Advanced settings
6
34
| 60
A6V11562455_en--_a
No.
Application
settings
Descriptions
Factory
settings
Range
Dependencies
35. Off/protection
configuration
Configures whether
the thermostat goes
to the protection
mode or completely
turns off in
OFF
mode.
Protection
Off
Protection
N/A
36. Heating
control loop
Indicates a different
time for PWM
(Pulse Width
Modulation) pulse
periods. You can
select the default
setting to let the
system configure
the most suitable
heating controller
settings based on
your selected
equipment type.
Default
Slow
Medium
Default
Fast
2-position
Self-
adaptive
N/A
37. Floor
temperature
limit
Floor temperature
limit for electric floor
heating
40 °C 35…60 °C Valid only if
you’ve
selected the
equipment type
as
Electric floor
heating
and
enabled the
floor
temperature
input in
Changing
system setup
[
➙
35].
38. Optimum start
control
Pre-heats the room
in an optimum way
so that you can get
the scheduled
temperature
setpoint at your
scheduled occupied
time. You can
choose
Warm-up
gradient
to manually
define the warm-up
speed, or choose
Self-adaptive
to let
the thermostat learn
and decide the
warm-up speed.
Warm-up
gradient
Warm-up
gradient
Self-
adaptive
Visible only if
you’ve
activated the
optimum start
control settings
in Changing
system setup
[➙ 35].
Other settings