User Manual

Operating the thermostat on the device
Advanced settings
A6V11562455_en
--_a
35 | 60
No.
Application
settings
Descriptions
Factory
settings
Range
Dependencies
39. Warm-up
gradient
The warm-up speed
that you set to pre-
heat the room.
30 min/K 0…120 mi
n/K
Valid only if
you’ve
activated the
optimum start
control settings
in Changing
system setup
[ 35]
and
selected
Warm-up
gradient
for
Application
setting No.38
To manage application settings
1. On the Home screen, tap , then tap and .
2. If prompted, enter the administrator password.
3. Tap > , and then scroll to the specific setting that you want to turn on/off or
change to a desired Value.
4. Tap to change the setting as desired.
6.8.3 Changing system setup
If you want to change any of your initial setup options that you’ve already
configured during the setup wizard, you can change them later under
Advanced
Settings. You can also change some other default system setup options to suit
your own needs. However, we recommend that only installers or experts with
detailed know-how about your thermostat modify the setup options.
See the Quick guide for guidance to the setup wizard.
Changing basic configurations of the thermostat allows you to change the
equipment type that your thermostat is working together with. The equipment could
be one of the following:
Gas boiler
Radiator with valve
Radiator with pump
Electric floor heating
Fan with electric heating
Floor heating with valve
Floor heating with pump
Electric radiator
Electric boiler
Generic heating device
If the selected equipment is related to a pump or valve, you can decide whether to
run the pump or valve periodically.
Changing basic
configurations