Operating the thermostat on the device
Advanced settings
6
36
| 60
A6V11562455_en--_a
NOTICE
When selecting the gas boiler application, ensure a hydronic heating is used. The
RDS110.R is not calibrated for use in combination with a gas-fired ducted heating
system.
To change basic configuration
1. On the Home screen, tap , then tap and .
2. If prompted, enter the administrator password.
3. Tap > .
4. Tap OK to stop all of your thermostat’s applications. Your thermostat restarts.
5. After the restart is completed, tap Equipment > Adapt.
6. If necessary, tap to scroll through all the listed equipment types and then
choose one as desired.
7. If the equipment is a pump or valve, choose whether to run the pump or valve
periodically by dragging the slider on the screen.
By changing extended configurations, you can:
● Change input assignments. Before you configure or change to another input, it
is strongly recommended that you’ve connected corresponding peripheral
devices to terminal X1 or X2. The input can be:
– Room temperature
– Operating mode switch
The thermostat switches to the OFF mode if you’ve configured the input as
Normally open. For example, if a thermostat in a hotel is configured to
Normally open for this input, when a hotel guest pulls out the room card, it
activates
Normally open. The thermostat switches to the OFF mode. Once
the room card is inserted again, the thermostat restarts the previously
running mode.
If X1 or X2 were assigned as Operating mode switch and the input
configured as
Normally open but physically terminal X1/X2 is not connected
to the related field devices, the thermostat may switch to the
OFF mode
and no longer functions normally unless changed to another input.
– Universal contact. A notification shows up in the mobile application when
the input status switches to
Normally closed (the circuit is closed). When
the status switches to
Normally open (the circuit is open), the notification
disappears.
– Floor temperature. This input is selectable only if you’ve configured the
equipment type as
Electric floor heating.
– Outside air temperature
– Room air humidity
– Presence detector
– Condensation monitor. If you’ve configured a condensation monitor as an
input, the condensation monitor detects the formulation of condensation on
chilled ceilings or at critical spots of heating or ventilation systems. If there
is a threat of condensation, the thermostat sends a warning signal for your
control actions. The same signal is also sent to the mobile application if the
Condensation monitor function is activated in the application.
● Change input signal types based on the input type you’ve assigned. The
following signal types are supported:
NOTICE! If you haven’t configured the corresponding application, some inputs
may not be selectable.
Changing extended
configurations