Cerberus™ PRO Test units and accessories FDUL221, DX791, RE6, REF8, REF8-S, REF8-C, RE8, RE8-S, RE8-C, RE7T, RE8ST, RE8STCO, RE8-CO, RE7T-x, RE10, FDUM29x, FDLU291, LE3, StabexHF Test units to test detectors and detector lines for FS720 fire detection installations.
Line tester FDUL221 Properties ● ● ● ● ● ● ● 4-line display with 20 characters per line Menu-guided operation Supply with battery or via network adapter Possible to update the device software (firmware) via the MCL-USB adapter (radio) FDUZ227 and via a PC Environmentally friendly processing Reusable materials Electronic parts and synthetic materials can be easily separated Function Different functions can be called up, e.g.
Fig.
Use The line tester FDUL221 is a universal device for the final testing of fully installed C-NET fire detector lines if a control panel is not connected. The device is used to for error searches by the electrician, installer, or service technician.
Detector exchanger DX791, adapter FDUD491 Properties ● ● Lightweight, robust design, made from reusable, environmentally friendly material Possible to exchange the detector without a ladder or scaffolding up to a room height of 8 m with the help of the telescope rods The point detector can be held in all positions.
Detector tester RE6 ● ● ● ● The detector tester RE6 is used together with a test gas can REF8, REF8-S, or REF8-C. It is designed to test optical smoke detectors, ionization detectors, and CO detectors. The detector tester is positioned over the detector for the testing process. Brief pressure causes the test gas to flow into the measuring chamber of the detector and therefore simulate the presence of fire aerosols. After a short period of time, the detector responds and triggers the alarm.
Detector tester RE7T – Solo461 heat detector tester kit The heat detector tester kit consists of ● 1x heat detector tester ● 2x rechargeable batteries ● 1x charger with 12 V connection cable ● 2x mains cables AC 110/120-220/240 V. The heat detector tester contains a hot air generator. The heat detector tester is positioned over the detector for the function check. The hot air emitted heats the detector which triggers this alarm.
Detector tester RE8ST – Testifire 1001-101 RT test kit The test kit RE8ST consists of ● 1x Testifire 1001-101 tester ● 1x RE8-S smoke capsule ● 2x rechargeable batteries ● 1x charger with 12 V connection cable ● 2x mains cables AC 110/120-220/240 V ● 1x USB cable. The detector tester contains a smoke capsule. The detector tester is positioned over the detector for the function check. The smoke that is emitted triggers an alarm.
Detector tester RE8STCO – Testifire 1001-101 ST test kit Fig. 4: The test kit RE8STCO consists of ● 1x Testifire 2001-101 tester ● 1x RE8-S smoke capsule ● 1x RE8-CO CO capsule ● 2x rechargeable batteries ● 1x charger with 12 V connection cable ● 2x mains cables AC 110/120-220/240 V ● 1x USB cable. The detector tester contains a smoke capsule or CO capsule. The detector tester is positioned over the detector for the function check. The smoke or gas that is emitted triggers an alarm.
Accessories and spare parts for RE7T/RE8ST/RE8STCO RE7T-A – Solo719 adapter for FDUM29x Mounting adapter for the detector testers RE7T, RE8ST, and RE8STCO on the telescope rods FDUM291 and FDUM292 RE7T-B1 – Solo770 battery Battery as spare part RE7T-C1 (Solo727 charger) Charger as spare part for charging the batteries RE7T-B1 RE8-S smoke capsule for RE8ST and RE8STCO RE8-CO CO capsule for RE8STCO 10 Smart Infrastructure A6V10203222_n_en_-2021-09-03
Telescope rods FDUM291 and FDUM292 Properties ● ● ● ● ● ● Light and robust yellow plastic pipes, non-conductive material Plastic sockets and friction bearings ensure that the pipes run into each other easily. Quick spring-type locking mechanisms allow continuous adjustment of the length. The pipes can be extended to their maximum length. A stop is used to prevent them from extending further. Existing testers can be used. The telescope rods cannot be extended.
FDUM291 ● ● ● ● ● ● Light telescope rod for all applications in rooms up to 5.5 m high Flap closure for continuous adjustment of the length Three-part telescope with tri-oval pipes as practical grip Twisting the pipe in the opposite direction is not possible Weight: 1.2 kg without tester fitted Retracted length 1.6 m, extended length 4.
Detector tester RE10, alarm test filter TF04 ● ● For undertaking a function check on the linear smoke detectors. The alarm test filter TF04 is inserted into the detector tester in accordance with the type of detector to be tested. An alarm test filter is also included in the adjustment kit FDLU291. For testing, the detector tester is held in front of the detector lens in the IR beam. The detector responds after a few seconds.
LE3 Test lamp The test lamp LE3 is used to test the function of all flame detectors over distances up to 10 m. It is housed in a transportable case together with the required accessories. In addition, the case enables the test lamp to be kept in a dust-free condition. The quartz-halogen lamp used creates an intense ray of light. This helps to align the lamp on the detector which is to be tested. During the detector test, the ray of light is modulated.
Technical data Line tester FDUL221 Supply voltage Battery or via network adapter Min. DC 10 V, max. DC 30 V Lithium manganese dioxide battery 1, 2x 9 V AC 240 V / DC 24 V, 750 mA Power consumption during measurement Depends on the number of devices and the display backlight Detector line voltage: C-NET (FS720) C-NET DC 32 V DC 28 V Max. detector key figures (MK) per line: MK with network adapter MK with battery Min. 550 Min.
Test lamp LE3 Power consumption 50 W Modulation frequency 4 Hz Max. distance for alarm activation 10 m Measuring capacity with charged battery and max. distance Number of detectors ~ 50 Operating and storage temperature -20...+ 45 °C Areas of use Areas not at risk of explosion Incandescent lamp Halogen 12 V / 50 W Battery 12 V / 7 Ah, lead, gas tight Charging time Min.
Details for ordering Type Order number Designation Line tester FDUL221 A5Q00004397 Line tester with line connection kit FDUL221-A, power unit set FDUL221-B and carry case 1.567 kg Accessories – A5Q00004142 Lithium manganese dioxide battery 9 V / 1.2 Ah 0.035 kg Spare part FDUL221-A A5Q00008436 Line connection kit 0.088 kg FDUL221-B A5Q00008437 Power unit kit 0.278 kg FDUL221-C A5Q00008438 RS232 PC cable as spare part for FDUL221 with RS232 interface 0.
Type Order number Designation Telescope rod FDUM292 A5Q00004997 Telescope rod – four-part telescope with round pipes, 2.1 m / 7.3 m 4.480 kg Spare part – A5Q00009787 Lever with screw and nut, flip top closure 0.023 kg – A5Q00009786 Adapter with lever, screw, and nut incl. mounting and sleeve bolt 0.088 kg Type Order number Designation Detector tester RE10 BPZ:3685190001 Detector tester for linear smoke detectors 0.
Applicable documents Document ID Name A6V10229261 List of compatibility (for 'Cerberus™ PRO' product line) A6V10201731 Installation Detector exchanger DX791, adapter for detector exchanger FDUD491 A6V10254740 Operating instructions Solo461 heat detector tester kit RE7T A6V10387053 Installation RE8ST Testifire 1001-101 ST test kit, RE8STCO Testifire 2001-101 STCO test kit A6V10260320 Operation RE7T-C Solo726 charger for RE7T-B A6V11432110 Operation RE7T-C1 Solo727 charger for RE7T-B1 Solo770 00
Issued by Siemens Switzerland Ltd Smart Infrastructure Global Headquarters Theilerstrasse 1a CH-6300 Zug +41 58 724 2424 www.siemens.com/buildingtechnologies Document ID A6V10203222_n_en_-- Edition 2021-09-03 © Siemens Switzerland Ltd, 2008 Technical specifications and availability subject to change without notice.