The expert level is quit by pressing the operating mode selection button .
Code list
Function block Code Name Factory setting Your setting
Basic settings
00 Language English
01 Sensor calibration off
02 Switching differential 0.5 °C
LCD settings
10 Illumination time 10 seconds
11 Background brightness 0
12 Contrast 0
Clock settings
30
Time zone
Deviation from time signal received from Frankfurt
(Central European Time CET) (refer to Note 1)
0 hours
31 Start of summer time (refer to Note 2) March 31 (31-03)
32 End of summer time (refer to Note 3) October 31 (31-10)
Note 1: If the radio clock is not active or not present, this setting has no impact.
With the radio clock active, the time signal received from Frankfurt is shifted by the value set under code 30 (time zone).
Note 2: If the radio clock is not active or not present, the time change always takes place at 02:00 on the Sunday before the set date.
With the radio clock active, the time change is shifted by the value set under code 30 (time zone).
Note 3: If the radio clock is not active or not present, the time change always takes place at 03:00 on the Sunday before the set date.
With the radio clock active, the time change is shifted by the value set under code 30 (time zone).
3 Function check
a) Check the display. If there is no display, check the batteries
b) “Continuously Comfort mode“
, read the temperature displayed
c) REV.. in heating mode: Set the temperature setpoint to a level above the
displayed room temperature (see operating instructions).
REV.. in cooling mode: Set the temperature setpoint to a level below the
displayed room temperature (see operating instructions).
d) The relay and thus the actuating device must respond within
1 minute. Symbol appears on the display. If not:
· Check actuating device and wiring
· In heating mode, the room temperature is possibly higher than the
adjusted temperature setpoint, in cooling mode possibly lower
e) Set temperature setpoint of “Continuously Comfort mode“ to the
required level
f) Select the required operating mode
4 Reset
User-defined settings:
Press simultaneously
, and for 3 seconds:
All temperature and time settings of the slider positions are reset to their default
values (refer to section “Factory settings“ in the operating instructions). The
settings made on the expert level will remain unchanged.
The clock starts at 12:00, the date on 01-01-08
(01 - January - 2008). During the reset time, all sectors of the display are
illuminated and can thus be checked.
All user-defined settings plus those made on the expert level:
Press simultaneously the DIP switch reset button, and for 5
seconds:
After this reset, all factory settings will be reloaded. This applies to both the
slider settings and the settings made on the expert level.
Notes
· The controller is classified as a device of software class A and designed
for use in environments with normal degree of pollution
· REV24RF/SET is a set of units consisting of electronic room temperature
controller with 7-day time switch, RF transmitter (REV24RF..) and RF
receiver (RCR10/868)