System Manual
Table Of Contents
- SIMATIC RF200
- Legal information
- Table of contents
- 1 Introduction
- 2 Safety notes
- 3 System overview
- 4 Planning the RF200 system
- 4.1 Fundamentals of application planning
- 4.1.1 Selection criteria for SIMATIC RF200 components
- 4.1.2 Transmission window and read/write distance
- 4.1.3 Width of the transmission window
- 4.1.4 Impact of secondary fields
- 4.1.5 Permissible directions of motion of the transponder
- 4.1.6 Operation in static and dynamic mode
- 4.1.7 Dwell time of the transponder
- 4.1.8 Communication between communication module, reader and transponder
- 4.2 Field data of transponders and readers
- 4.3 Installation guidelines
- 4.4 Chemical resistance of the reader and transponders
- 4.5 Further information
- 4.1 Fundamentals of application planning
- 5 Readers
- 5.1 SIMATIC RF210R
- 5.2 SIMATIC RF210M
- 5.3 SIMATIC RF220R
- 5.4 SIMATIC RF240R
- 5.5 SIMATIC RF250R
- 5.6 SIMATIC RF260R
- 5.7 SIMATIC RF280R
- 5.8 SIMATIC RF285R
- 5.9 SIMATIC RF290R
- 6 Antennas
- 7 Transponder
- 7.1 Memory configuration of ISO the transponders
- 7.2 MDS D100
- 7.3 MDS D117
- 7.4 MDS D124
- 7.5 MDS D126
- 7.6 MDS D127
- 7.7 MDS D139
- 7.8 MDS D160
- 7.9 MDS D165
- 7.10 MDS D200
- 7.11 MDS D261
- 7.12 MDS D324
- 7.13 MDS D339
- 7.14 MDS D400
- 7.15 MDS D421
- 7.16 MDS D422
- 7.17 MDS D423
- 7.18 MDS D424
- 7.19 MDS D425
- 7.20 MDS D426
- 7.21 MDS D428
- 7.22 MDS D460
- 7.23 MDS D521
- 7.24 MDS D522
- 7.25 MDS D522 special variant
- 7.26 MDS D524
- 7.27 MDS D525
- 7.28 MDS D526
- 7.29 MDS D528
- 7.30 MDS D560
- 8 System integration
- 9 System diagnostics
- A Appendix
Readers
5.9 SIMATIC RF290R
SIMATIC RF200
182 System Manual, 03/2019, J31069-D0227-U001-A11-7619
5.9.4 LED operating display
The operational statuses of the reader are displayed by the LEDs. The LED can adopt the
colors green, red or yellow and the statuses off
, on , flashing :
Table 5- 25 LED operating display on the reader
Labeling
LED
Meaning
PWR
The reader is turned off.
PWR
CM mode:
Operating voltage present, reader not initialized or antenna
switched off
CM mode:
Operating voltage present, reader initialized and antenna switched
on
PC mode:
Supply voltage is on
ACT
Communication on the data line
PRE
• Operating mode "with presence": Transponder present
• Operating mode "without presence": Transponder present and
command currently being executed
ERR
CM mode:
There is an error. The number of flashes provides information
about the current error. You can find more information on error
messages in the section "Error codes of the RF200 readers
(Page 409)". The optical error display is only reset if the corre-
sponding reset parameter ("option_1 = 2") is set (see Product In-
formation " Product information "SIMATIC RF200 command set"
(https://support.industry.siemens.com/cs/ww/en/view/44864850)").
PC mode:
Error when connecting the antenna or the interference level in the
antenna environment is too high