7.24 MDS D522
SIMATIC RF200
376 System Manual, 03/2019, J31069-D0227-U001-A11-7619
Mounting information for screws
You can screw the transponder into a pre-drilled threaded hole using the screw-in aid.
Mounting information for adhesion
Drill installation hole
The adhesive surfaces must be dry, free from dust, oil, stripping agents and other
impurities
Apply adhesive according to the manufacturer's processing instructions
Press in MDS D522 using your fingers; with antenna to the outside
Remove residues of adhesive
Allow to cure according to the manufacturer's instructions
Flush-mounting of MDS D522 in metal with tools
7.24.4 Technical specifications
Table 7- 62 Technical specifications for MDS D522
6GT2600-5AF00
Product type designation
SIMATIC MDS D522
Memory
Memory configuration
UID 8 bytes
User memory 8192 bytes FRAM
Read cycles (at < 40 ℃)
> 10
12
Write cycles (at < 40 ℃)
> 10
12
Data retention time (at < 40 ℃)
> 10 years
Write/read distance (S
g
) Dependent on the reader used, see section "Field
data (Page 39)"
MTBF (Mean Time Between Failures)
285 years
Mechanical specifications
Enclosure
Material Plastic PA 6.6 GF; brass nickel plated
Color Black/silver
Recommended distance to metal
≥ 0 mm
Power supply
Inductive, without battery