System Manual

Table Of Contents
Planning the RF200 system
4.3 Installation guidelines
SIMATIC RF200
System Manual, 03/2019, J31069-D0227-U001-A11-7619
65
Table 4- 32 Reduction of field data due to metal, range as %: Transponder and RF210R
Transponder
Reader without direct
metal influence
(Case a, b and d)
Reader flush-
mounted in metal
(Case c)
MDS D124
1)
Metal-free
100
82
On metal, distance 15 mm
90
90
Flush-mounted in metal;
distance all round 15 mm
85 80
MDS D127
Flush-mounted in metal;
distance all round 0 mm
100 75
MDS D160
1)
Metal-free
100
95
On metal, distance 10 mm
100
95
MDS D324
1)
Metal-free
100
90
On metal, distance 15 mm
90
90
Flush-mounted in metal;
distance all round 25 mm
80 90
MDS D421
Metal-free
100
90
Flush-mounted in metal;
distance all round 0 mm
75 50
MDS D422
Metal-free
100
80
Flush-mounted in metal;
distance all round 0 mm
90 40
MDS D423
Metal-free
100
90
On metal, distance 0 mm
110
2)
100
2)
Flush-mounted in metal;
distance all round 10 mm
95 85
MDS D424
1)
Metal-free
100
60
On metal, distance 15 mm
90
80
Flush-mounted in metal;
distance all round 25 mm
85 75
MDS D425
Metal-free
100
85
On metal, distance 0 mm
100
85
MDS D428
Metal-free
100
90
On metal, distance 0 mm
100
80
MDS D460
1)
Metal-free
100
90
On metal, distance 25 mm
100
90
MDS D521
Metal-free
100
90
Flush-mounted in metal;
distance all round 0 mm
75 50