System Manual
Table Of Contents
- SIMATIC RF200
- Legal information
- Table of contents
- 1 Introduction
- 2 Safety notes
- 3 System overview
- 4 Planning the RF200 system
- 4.1 Fundamentals of application planning
- 4.1.1 Selection criteria for SIMATIC RF200 components
- 4.1.2 Transmission window and read/write distance
- 4.1.3 Width of the transmission window
- 4.1.4 Impact of secondary fields
- 4.1.5 Permissible directions of motion of the transponder
- 4.1.6 Operation in static and dynamic mode
- 4.1.7 Dwell time of the transponder
- 4.1.8 Communication between communication module, reader and transponder
- 4.2 Field data of transponders and readers
- 4.3 Installation guidelines
- 4.4 Chemical resistance of the reader and transponders
- 4.5 Further information
- 4.1 Fundamentals of application planning
- 5 Readers
- 5.1 SIMATIC RF210R
- 5.2 SIMATIC RF210M
- 5.3 SIMATIC RF220R
- 5.4 SIMATIC RF240R
- 5.5 SIMATIC RF250R
- 5.6 SIMATIC RF260R
- 5.7 SIMATIC RF280R
- 5.8 SIMATIC RF285R
- 5.9 SIMATIC RF290R
- 6 Antennas
- 7 Transponder
- 7.1 Memory configuration of ISO the transponders
- 7.2 MDS D100
- 7.3 MDS D117
- 7.4 MDS D124
- 7.5 MDS D126
- 7.6 MDS D127
- 7.7 MDS D139
- 7.8 MDS D160
- 7.9 MDS D165
- 7.10 MDS D200
- 7.11 MDS D261
- 7.12 MDS D324
- 7.13 MDS D339
- 7.14 MDS D400
- 7.15 MDS D421
- 7.16 MDS D422
- 7.17 MDS D423
- 7.18 MDS D424
- 7.19 MDS D425
- 7.20 MDS D426
- 7.21 MDS D428
- 7.22 MDS D460
- 7.23 MDS D521
- 7.24 MDS D522
- 7.25 MDS D522 special variant
- 7.26 MDS D524
- 7.27 MDS D525
- 7.28 MDS D526
- 7.29 MDS D528
- 7.30 MDS D560
- 8 System integration
- 9 System diagnostics
- A Appendix
Planning the RF200 system
4.3 Installation guidelines
SIMATIC RF200
80 System Manual, 03/2019, J31069-D0227-U001-A11-7619
Transponder
RF250R with ANT 30
Antenna without
metal
Antenna flush-
mounted in metal
(all round 20 mm)
MDS D423
Without metal
100
90
On metal, distance 0 mm
130
2)
110
2)
Flush-mounted in metal;
distance all round 10 mm
80 70
MDS D424
1)
Without metal
100
85
On metal, distance 15 mm
90
75
Flush-mounted in metal;
distance all round 25 mm
75 70
MDS D425
Without metal
100
90
On metal, distance 0 mm
95
75
MDS D426
1)
Without metal
100
70
On metal, distance 25 mm
90
65
Flush-mounted in metal;
distance all round 25 mm
55 45
MDS D428
Without metal
100
90
On metal, distance 0 mm
100
90
MDS D460
1)
Without metal
100
85
On metal, distance 10 mm
90
75
MDS D522
Without metal
100
95
Flush-mounted in metal;
distance all round 0 mm
95 80
MDS D522
Special variants
Without metal
100
95
Flush-mounted in metal;
distance all round 0 mm
95 80
MDS D524
1)
Without metal
100
85
On metal, distance 15 mm
90
75
Flush-mounted in metal;
distance all round 25 mm
75 70
MDS D526
1)
Without metal
100
70
On metal, distance 25 mm
90
65
Flush-mounted in metal;
distance all round 25 mm
55 45
MDS D528
Without metal
100
90
On metal, distance 0 mm
100
90
MDS D560
1)
Without metal
100
85
On metal, distance 10 mm
90
75
1)
Mounting the transponder on or in metal is only possible with the appropriate spacer or if there is
adequate clearance to the metal.
2)
Values of > 100 % related to non metal surroundings can occur if transponders were developed
specifically for mounting in/on metallic surroundings.