System Manual
Table Of Contents
- SIMATIC RF200
- Legal information
- Table of contents
- 1 Introduction
- 2 Safety notes
- 3 System overview
- 4 Planning the RF200 system
- 4.1 Fundamentals of application planning
- 4.1.1 Selection criteria for SIMATIC RF200 components
- 4.1.2 Transmission window and read/write distance
- 4.1.3 Width of the transmission window
- 4.1.4 Impact of secondary fields
- 4.1.5 Permissible directions of motion of the transponder
- 4.1.6 Operation in static and dynamic mode
- 4.1.7 Dwell time of the transponder
- 4.1.8 Communication between communication module, reader and transponder
- 4.2 Field data of transponders and readers
- 4.3 Installation guidelines
- 4.4 Chemical resistance of the reader and transponders
- 4.5 Further information
- 4.1 Fundamentals of application planning
- 5 Readers
- 5.1 SIMATIC RF210R
- 5.2 SIMATIC RF210M
- 5.3 SIMATIC RF220R
- 5.4 SIMATIC RF240R
- 5.5 SIMATIC RF250R
- 5.6 SIMATIC RF260R
- 5.7 SIMATIC RF280R
- 5.8 SIMATIC RF285R
- 5.9 SIMATIC RF290R
- 6 Antennas
- 7 Transponder
- 7.1 Memory configuration of ISO the transponders
- 7.2 MDS D100
- 7.3 MDS D117
- 7.4 MDS D124
- 7.5 MDS D126
- 7.6 MDS D127
- 7.7 MDS D139
- 7.8 MDS D160
- 7.9 MDS D165
- 7.10 MDS D200
- 7.11 MDS D261
- 7.12 MDS D324
- 7.13 MDS D339
- 7.14 MDS D400
- 7.15 MDS D421
- 7.16 MDS D422
- 7.17 MDS D423
- 7.18 MDS D424
- 7.19 MDS D425
- 7.20 MDS D426
- 7.21 MDS D428
- 7.22 MDS D460
- 7.23 MDS D521
- 7.24 MDS D522
- 7.25 MDS D522 special variant
- 7.26 MDS D524
- 7.27 MDS D525
- 7.28 MDS D526
- 7.29 MDS D528
- 7.30 MDS D560
- 8 System integration
- 9 System diagnostics
- A Appendix
Planning the RF200 system
4.3 Installation guidelines
SIMATIC RF200
System Manual, 03/2019, J31069-D0227-U001-A11-7619
83
Transponder
Reader with-
out metal
direct metal
influence
Reader on met-
al
(metal plate)
Reader flush-
mounted in metal
(all round 20 mm)
MDS D526
1)
Without metal
100
100
73
On metal, distance 25 mm
88
85
68
Flush-mounted in metal;
distance all round 50 mm
3)
65 55 55
MDS D528
Without metal
100
90
90
On metal, distance 0 mm
90
90
85
MDS D560
1)
Without metal
100
95
90
On metal, distance 10 mm
90
85
80
1)
Mounting the transponder on or in metal is only possible with the appropriate spacer or if there is
adequate clearance to the metal.
2)
Transponder flush-mounted in metal; minimum distance to reader 5 mm
3)
Transponder flush-mounted in metal; minimum distance to reader 10 mm
4)
Transponder flush-mounted in metal; minimum distance to reader 15 mm
5)
Values > 100 % can occur if transponders were developed specifically for mounting in/on metallic
surroundings.
4.3.4.6 RF280R
The RF280R can be flush-mounted in metal. Please allow for a possible reduction in the field
data values. To avoid reduction, the distance a should be ≥ 20 mm.
Figure 4-13 Metal-free area RF280R