System Manual

ISO transponder
8.12 MDS D324
SIMATIC RF300
System Manual, 07/2017, C79000-G8976-C345-07
323
Flush-mounting
h
≥ 15 mm
a
≥ 25 mm
Figure 8-26 Flush-mounting of the MDS D124/D324/D424/D524/E624 and RF320T in metal with
spacer
Note
Going below the distances
If the distances (a and h) are not observed, a reduction of the field data results. It is possible
to mount the MDS with metal screws (M3 counters
unk head screws). This has no tangible
impact on the range.
8.12.4
Technical specifications
Table 8- 30 Technical specifications of MDS D324
6GT2600-3AC00
SIMATIC MDS D324
Memory
UID 8 bytes
User memory 992 bytes EEPROM
OTP memory 16 bytes (EEPROM)
> 10
14
> 10
6
> 10 years