User Manual
  GAMMA instabus 
Technical product information 
August 2020 
Shutter / blind actuator (RL module) RL 521/23  5WG1521-4AB23 
AC 230V, 2 x 6A, with detection of end positions 
Siemens Switzerland Ltd  RS-AG   
Building Technologies Division 
International Headquarters    
Theilerstrasse 1a  © Siemens AG 2020  Update: http://www.siemens.com/gamma 
CH-6300 Zug  Subject to changes 
    1 
Product and functional description 
The RL 521/23 shutter / blind actuator is a KNX device with 
two  relay  output  channels.  The  device  is installed  in an 
AP 118  Control  Module  Box  or  an  AP 641  room control 
box. The bus is connected via a bus terminal  block. The 
actuator electronics are supplied via the bus voltage. 
The RL 521/23 may be used to control blinds, shutters, 
awnings, windows, or doors. 
The device is designed to drive (per channel) one AC 230V 
drive  (motor)  with  electromechanical  limit  switches  or 
with integrated electronics for disconnection at the limit 
positions. 
For drives with electromechanical limit switches the actu-
ator can be configured to detect the status of the electro-
mechanical  limit  switches  such  that  the  travel  time  be-
tween the end positions can be measured via a synchroni-
zation run. The travel time of the blind / shutter is auto-
matically measured  from  the  upper  end  position  to  the 
lower end  position  and  vice  versa. The  measurement  is 
only  reliable  for  drives  with  electromechanical  limit 
switches.  The  travel  time  cannot  be  automatically  ad-
justed for drives with integrated electronics for disconnec-
tion  at  the limit  positions. These  drives  have  to be con-
trolled via a time limit. Their travel times have to be man-
ually measured as precisely as possible and configured in 
the application program. 
Parallel  operation  of  several  drives  on  one  channel  re-
quires the intermediate switching of a special separation 
relay. If such a separation relay is connected to the output 
to drive several drives in parallel, then the travel time has 
to be configured manually. 
If the device is configured for automatic detection of the 
travel time, then parallel operation of several drives with 
electromechanical limit switches or mixed operation with 
drives with integrated electronics for disconnection at the 
limit positions is not permitted. 
Detection of final positions, Automatic detection of 
travel times 
The device can detect if the blind / shutter is in the upper 
or lower end position. This detection depends on the solar 
protection drive (motor) itself and on the wiring and spe-
cifically cannot be guaranteed for drives with integrated 
electronics for disconnection at the limit positions. Hence, 
the detection can be disabled by a parameter. If automatic 
detection of end positions is enabled, the travel time is set 
to the maximum value after a download of the configura-
tion. If the end positions were detected successfully and 
the solar protection moved without interruption from the 
lower position to the upper position, then the parameter 
value for the travel time is updated and saved. The same 
applies to the travel time from the upper to the lower end 
position. 
When the  end  position is  detected,  then the  parameter 
value for the  travel  time extension is set to  10% of  the 
travel time. In principal, the travel time, i.e. the time the 
relay contacts are closed, is determined based on the con-
figured  value  or  the  parameter value  updated  based on 
the travel times measured between end positions 
After a download of the application program respectively 
of addresses and parameters the solar protection must be 
synchronized.  This  is  triggered  when  a  telegram  “solar 
protection up/down” or “central up/down” is received. The 
solar protection then performs a synchronization run. First 
it briefly moves down, then fully into the upper end posi-
tion.  Then it  moves  from  the upper end  position  to the 
lower end position measuring the associated travel time. 
Finally, it moves from the lower end position to the upper 
end position measuring the associated travel time. After 
this procedure the solar protection is synchronized and re-
mains in the upper end position until a motion is triggered 
by another telegram.  
If the actuator does not detect the upper end position at 
the  start of the synchronization  run,  then the measure-
ment travels are not executed. In that case, the actuator is 
not synchronized. The synchronization run has to be initi-
ated again as described above. 
Any  additional  telegram  “solar  protection  up/down”  or 
“central  up/down”  received  during  the  synchronization 
run is ignored. If a telegram “slats open/close” is received 
this  is  interpreted  as  stop  and  the  solar  protection  is 
stopped  without  finalizing  the  synchronization  of  the 








