Basic Documentation

13.3 Configuration
13.3.1 Explanation of configuration principle
The controller includes a large number of preconfigured function blocks. The
function blocks available for the various RLU2… universal controllers are shown in
the respective configuration diagrams. They include:
Configuration
diagrams, contents
Input identifiers (inputs, input functions)
Function blocks for open and closed-loop control functions
Aggregates (outputs, output functions)
Project engineers can add connections from the individual input and output
functions (i.e. their internal signals) to the assigned terminals.
Configuration
diagrams, contents
Physical inputs:
Designations used
D digital
X universal
Physical outputs:
Q relay
Y DC 0…10 V
The following rules and properties apply to inputs:
Use of inputs Xx
The input identifier can be a device or a special sensor:
Room temperature (ROOM), outside temperature (OUTS), frost protection
(FRST), remote setpoint adjuster, absolute (REL) or relative (REL)
Multiple use of inputs is possible without limitation (e.g. room temperature as the
main controlled variable and as the maximum economy changeover criterion for
the air damper)
When an input is connected, the controller presents only the possible units on
the display
The error message for inputs is only active if the input is connected before
completion of commissioning
If you change an input identifier (LABEL), all of the settings associated with it
also change (e.g. Xp used to be 28 K, and now it is 10 Pa)
157 / 174