Basic Documentation

Path: … > PARA > STEP V1
Setting values
… > PARA > STEP V2
Display Name Range Factory setting
S1-ON [Step 1] ON 0…100 % 17 %
S1-OFF [Step 1] OFF 0…100 % 1 %
S2-ON [Step 2] ON 0…100 % 33 %
S2-OFF [Step 2] OFF 0…100 % 17 %
S3-ON [Step 3] ON 0…100 % 50 %
S3-OFF [Step 3] OFF 0…100 % 33 %
S4-ON [Step 4] ON 0…100 % 67 %
S4-OFF [Step 4] OFF 0…100 % 50 %
S5-ON [Step 5] ON 0…100 % 83 %
S5-OFF [Step 5] OFF 0…100 % 67 %
S6-ON [Step 6] ON 0…100 % 100 %
S6-OFF [Step 6] OFF 0…100 % 83 %
OFFTIME Locking time 00.00…10.00 m.s 00.00 m.s
MIN POS Positioning signal min 0…100 % 0 %
MAX POS Positioning signal max 0…100 % 100 %
INVERS Inversion NO, YES NO
Note STEP V1 has a maximum of 2 steps.
Therefore, the setting values for S3-ON to S6-OFF are not shown.
Path: INFO
Display values
Display Name Comments
STEP V1 Variable step switch 1 0…100 %
STEP x Variable step switch 1, step x ON, OFF
STEP V2 Variable step switch 2 0…100 %
STEP x Variable step switch 2, step x ON, OFF
Path: … > COMMIS > TEST
Wiring test
Display Name Positions
STEP V1 Variable step switch 1 ---, 0…100 %
STEP x Variable step switch 1, step x ON, OFF
STEP V2 Variable step switch 2 ---, 0…100 %
STEP x Variable step switch 2, step x ON, OFF
78 / 174
Siemens Universal Controllers RLU2… CE1P3101en
Building Technologies Aggregates 29.08.2008