User Manual
8.3.11 Start condition 1, 2, 3, 4
The start condition inputs are required to:
Define the load from several signals to start several aggregates.
Generate an analog load signal from several signals.
The start conditions are not evaluated until the precommand input is On if a
precommand input is configured and the precommand input state is Off.
Note
Main menu > Commissioning > Extra configuration > Aggregates > Rotary step switch >
Rotary step switch 1…2 >
Config
uration
Operating lin
e Adjustable values / Comment
Start condition 1 ---, X1, X2, ...
Start condition 2 ---, X1, X2, ...
Start condition 3 ---, X1, X2, ...
Start condition 4 ---, X1, X2, ...
You can set "[switching value n] On" and "[switching value n] Off" for inputs "Start
condition 1..4" to create a digital signal from a modulating signal.
Setting values
Enter the value in percent that is to be effective during switch-on of the
corresponding start condition via "[switching n] load".
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Aggregates > Rotary step switch > Rotary step switch 1…2 >
Operating line Range Factory setting
[Switching value 1] on Depending on selected type Type-dependent
[Switching value 1] off Depending on selected type
Type-dependent
[Switching value 1] load 0…100 %
25 %
[Switching value 2] on Depending on selected type Type-dependent
[Switching value 2] off Depending on selected type
Type-dependent
[Switching value 2] load 0…100 %
25 %
[Switching value 3] on Depending on selected type Type-dependent
[Switching value 3] off Depending on selected type
Type-dependent
[Switching value 3] load 0…100 %
25 %
[Switching value 4] on Depending on selected type Type-dependent
[Switching value 4] off Depending on selected type
Type-dependent
[Switching value 4] load 0…100 %
25 %
8.3.12 Fault message for aggregates (A…D)
You can configure a fault message for aggregates A…D if you want the aggregate
to switch off in a controlled manner in the event of a fault. Changeover selects the
next available aggregate in the linear rotary step switch.
104 / 216
Siemens Switching and monitoring device RMS705B CE1P3124en
Building Technologies Aggregates 01.04.2010