Main menu > Commissioning > Extra configuration > Aggregates > Rotary step switch >
Rotary step switch 1…2 >
Config
uration
Operating lin
e Adjustable values / Comment
Fault status message A ---, X1, X2, ...
Fault status message B ---, X1, X2, ...
Fault status message C ---, X1, X2, ...
Fault status message D ---, X1, X2, ...
The aggregate's priority is assigned without delay as per the run priority plan if a
fault message is removed after troubleshooting the aggregate. This may result in
changeover of the aggregates depending on the assigned priority.
8.3.13 Functional check
The current state of the rotary step switch is displayed on the operator unit.
Main menu > Aggregates > Rotary step switch 1…2 >
D
isplay values
Operating lin
e Comment
[Rot step swi 1A] precommand Off/On.
[Rot step swi 1A] command Off/On.
[Rot step swi 1A] load 0...100 %
[Rot step swi 1B] precommand Off/On.
[Rot step swi 1B] command Off/On.
[Rot step swi 1B] load 0...100 %
[Rot step swi 1C] precommand Off/On.
[Rot step swi 1C] command Off/On.
[Rot step swi 1C] load 0...100 %
[Rot step swi 1D] precommand Off/On.
[Rot step swi 1D] command Off/On.
[Rot step swi 1D] load 0...100 %
8.3.14 Assign texts
You can assign a text to each rotary step switch. The text is displayed on the menu
and in the operating line.
Main menu > Commissioning > Settings > .... or
Setting values
Main menu > Settings > Aggregates > Rotary step switch > Rotary step switch 1…2 >
Operating line Range Factory setting
Rotary step switch 1 Max. 20 characters Rotary step switch 1
See Section 16.4 "Editable texts RMS705B" for an overview of all editable texts
and on h
ow to reset them.
8.3.15 Troubleshooting
Run priority changeover is reset and started on the set default value following
power failure.