User Manual

Control of a twin pump by the motor block.
Example
X
You can enter a changeover period for orderly changeover of run priority.
Cha
ngeover period
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Aggregates > Motor > Motor 1...6 >
Setting values
Operating line Range Factory setting
Changeover period
60... 60 s
0 s
If a negative number is entered, both motors are switched on for the period of
time set during changeover.
If a positive number is entered, the second motor can switch on only after the
time has expired after the first motor has switched off.
Note The changeover period is also considered for the motor kick.
You can set a run-up time for the twin motor. The motor operating state is indicated
after the run-up time expires.
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Aggregates > Motor > Motor 1...6 >
Settings
Operating lin
e Range Factory setting
Runup time 00.00... 59.59 m.s 00.10 m.s
111 / 216
Siemens Switching and monitoring device RMS705B CE1P3124en
Building Technologies Aggregates 01.04.2010