User Manual

You can change the following texts ex-works texts in the RMS705B at the
password level.
No. Text Effect
1318 [Mot 1] precom no checkb signal Urgent message; must be
acknowledged and reset.
1328 [Mot 2] precom no checkb signal Urgent message; must be
acknowledged and reset.
1338 [Mot 3] precom no checkb signal Urgent message; must be
acknowledged and reset.
1348 [Mot 4] precom no checkb signal Urgent message; must be
acknowledged and reset.
1358 [Mot 5] precom no checkb signal Urgent message; must be
acknowledged and reset.
1368 [Mot 6] precom no checkb signal Urgent message; must be
acknowledged and reset.
Fault messa
ges
8.4.10 Motor operating state
The output motor operating state indicates if the motor is running at full speed.
Set the time the motor needs to reach full speed via the run-up time.
Main menu > Commissioning > Settings > or
Settings
Main menu > Settings > Aggregates > Motor > Motor 1...6 >
Operating line Range Factory setting
Runup time 00.00…59.59 m.s 00.10 m.s
You can configure the output motor operating state
for all internal inputs.
Use the motor operating state
e.g. to send a checkback signal of the motor
state to the rotary step switch.
The signal can have value "On" or "Off". It is "On" after the run-up time expires.
TiRup
Off
On
Functio
n diagram
based on
1-speed motor
TiRup = Runup time
119 / 216
Siemens Switching and monitoring device RMS705B CE1P3124en
Building Technologies Aggregates 01.04.2010