8.5.2 Limitations
The modulating output (Y) can be limited at the top and bottom.
Main menu > Commissioning > Settings > .... or
Setting values
Main menu > Settings > Aggregates > Modulating outputs > Modulating output A...H >
Operating line Range Factory setting
Positioning signal min 0...100 % 0 %
Positioning signal max 0...100 % 100 %
Output 0...100 % then corresponds to "Positioning signal min" (Ymin) to
"Positioning signal max" (Ymax).
0 %
100 %
0 %
0 V
100 %
10 V
Y
Y
max
min
Y
Qs
3123D09
Functio
n diagram
Qs = Load demand from controller
Y´ = Inversion
Key
Y
ou can thus parameterize the output with a DC 5...7.5 V input suitable for
controlling a magnetic valve, for example.
The greater of the signals is valid (maximum selection) when the modulating output
of 3 controllers is controlled.
Maximum sel
ection
8.5.3 Output inversion
Any output can be inverted.
Main menu > Commissioning > Settings > .... or
Setting values
Main menu > Settings > Aggregates > Modulating outputs > Modulating output A...H >
Operating line Range Factory setting
Inversion No, Yes No
Meaning:
No: 0...100% load = 0...100% output.
Yes: 0...100% load = 100...0 % output.