11.2.1 Setpoints
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Controller 1...3 > Setpoints >
Operating line Range Factory setting
(type-dependent)
Setpoint high
Depending on selected type. 24 °C, 24 K, 60 %,
10 g/kg, 30 kJ/kg,
800 W/m2, 15 m/s,
100 bar, 1000 mbar, 1000
Pa, 1000 ppm, 100, 1000
Setpoint low
Depending on selected type. 21 °C, 21 K, 40 %,
6 g/kg, 20 g/kg,
20 kJ/kg, 600 W/m2,
10 m/s, 6 bar, 60 mbar,
400 Pa, 0 ppm, 60, 600
Setting values
The following applies to differential control:
Differential actual value = Main controlled variable – differential input.
Note on dif
ferential
control
Main menu > Controller 1...3 >
D
isplay values
Operating lin
e Comment
Actual value
Current setpoint
Main menu > Controller 1...3 >
Operating line Comment
[Sequence 1 \_ ] load Current controller output in 0...100%.
[Sequence 4 _/ ] load Current controller output in 0...100%.
168 / 216
Siemens Switching and monitoring device RMS705B CE1P3124en
Building Technologies Universal controller 01.04.2010