11.5 Eco setpoint changeover
N.X1 N.X2
3124Z25en
This function allows for changeover to Eco setpoints.
To activate this function, configure the relevant digital input. Enabling
Eco setpoint changeover is available at controllers 1...3.
Main menu > Commissioning > Extra configuration > Controller 1…3 >
Config
uration
Operating lin
e Adjustable values / Comment
Setpoint switch ---, N.X1, N.X2, ...
(digital values only).
Functio
n diagram
Seq. 1 Seq. 4
Setpoint
low
Eco Setpoint
low
11.5.1 Setpoints
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Controller 1...3 > Setpoints >
Operating line Range Factory setting (type-dependent)
Eco setpoint high
Depending on
selected type.
28 °C, 28 K, 80 %, 12 g/kg, 50 kJ/kg,
1000 W/m2, 15 m/s, 100 bar, 1000
mbar, 1000 Pa, 1500 ppm, 100, 1000
Eco setpoint low
Depending on
selected type.
19 °C, 19 K, 20 %, 4 g/kg, 0 kJ/kg,
200 W/m2, 0 m/s, 0 bar, 0 mbar, 0 Pa,
0 ppm, 0
Setting values
175 / 216