3.2 Basic configuration
Use the "Basic configuration" menu for the following settings:
Select basic type (only basic type S is available).
Assign extension modules to the controller position.
Internal configurations are deleted if you decide to later reset RMS705B to basic
type S.
Note
Main menu > Commissioning > Basic configuration >
Config
uration
Operating lin
e Adjustable values / remarks
Basic type S
Position 1
---, RMZ785, RMZ787(1), RMZ788(1)
Position 2
---, RMZ785, RMZ787(1), RMZ787(2), RMZ788(1), RMZ788(2)
Position 3
---, RMZ785, RMZ787(1), RMZ787(2), RMZ788(1), RMZ788(2)
Position 4
---, RMZ785, RMZ787(1), RMZ787(2), RMZ788(1), RMZ788(2)
3.2.1 Assign extension modules
You can extend RMS705B by appending extension modules.
Max. 4 extension modules can be connected to each RMS705B. Select from:
1x RMZ785: Universal module with 8 universal inputs.
2x RMZ787: Universal module with 4 universal inputs, 4 relay outputs.
2x RMZ788: Universal module with 4 universal inputs, 2 modulating
outputs, 2 relay outputs
The extension modules are activated when physically plugged in and configured in
terms of software (type, position).
Position 1 Position 2 Position 3 Position 4
Example
RMS705B RMZ785 RMZ787 (1) RMZ787 (2) RMZ788 (1)
Disco
nnect the system from power prior to attaching an extension module.
19 / 216
Siemens Switching and monitoring device RMS705B CE1P3124en
Building Technologies Commissioning 01.04.2010