User Manual
13.2.6 Troubleshooting
After expiration of a specific time (ca. 30 minutes), a fault message "[...X...] Sensor
error" is sent if the bus should receive a signal from an input, but the signal is not
vailable. a
No. Text Effect
5000 No bus power supply Non-urgent message; must not be
acknowledged.
5902 >1 identical LTE zone Non-urgent message; must not be
acknowledged.
6001 >1 identical device
address
Urgent message; must be
acknowledged.
Fault messa
ges
190 / 216
Siemens Switching and monitoring device RMS705B CE1P3124en
Building Technologies Communication 01.04.2010