User Manual

201 / 216
Siemens Switching and monitoring device RMS705B CE1P3124en
Building Technologies Appendix 01.04.2010
16.2.3 Overview of configuration diagrams
Basic configuration
Configuration Function
RMZ785
RMZ787 (1), (2)
RMZ788 (1), (2)
Add further inputs and outputs with extension modules RMZ785, RMZ787, and RMZ788.
Controller functions are configured to these inputs/outputs.
Specify which modules are connected to RMS705B in which order (position); max 4 modules.
Input identifiers
Inputs
(Section 5)
Configuration Functions
N.X1
Yx
SIGNAL Y
N.X1…RMZ788(2).X4 Enter input identifier
Units:
°C, %, g / kg, kJ / kg, W / m², m / s, bar, mbar, Pa, ppm, universal 000.0
(display with one decimal place), universal 0000 (display without decimal
place).
The unit is only required for presentation on the display. The unit presents
all unit-dependent settings (e.g. P-bands) on the unit.
Sensor for °C:
LG-Ni1000, 2xLG-Ni1000 (averaging), T1, Pt1000, DC 0…10 V, all other
units DC 0…10 V, adjustable range.
Digital (input for potential-free contacts).
Pulse (up to 25 Hz for mechanical source (Reed contact),
or up to 100 Hz for electronic source).
Special identifiers: Outside temperature, remote setpoint adjuster.
With the special identifiers, internal connections are taken directly from
RMS705B.
A name can be assigned to each input.
N.X1
OT
Outside temperature Outside temperature for the following functions:
Connect one outside temperature sensor.
The bus can be used to receive the outside temperature.
Sensor as listed above under "Sensor for °C.
N.X1
[Controller 1] rem setp adj
[Controller 2] rem setp adj
[Controller 3] rem setp adj
Rem setp1: Absolute for controller 1 to 3
(0…1000 or DC 0…10 V).
N.X1
Pulse Select input identifier "Pulse" for an input.
Connection of a pulse source (mechanical or electronic).
Pulse source type can be assigned to the input.