Siemens Switching and monitoring device RMS705B CE1P3124en
Building Technologies Appendix 01.04.2010
Universal controller
Universal controller
(Section 11)
Configuration Functions
Main controlled variable
Differential input
Universal shift
General limiter
Input setpoint changeover
Start condition
Sequence outputs
3 universal controllers, can be used as a P, PI or PID controller.
Differential control possible.
Universal shift for setpoints.
Min./max limitation function.
Connection of remote setpoint adjuster.
Controller can be enabled via start input.
1 heating sequence S1, (\_); 1 cooling sequence S4, (_/).
A name can be assigned to each controller.
Faults
Faults
(Section 12)
Configuration Functions
Faults
Fault button external
Fault input 1 to 20
Fault relay 1 and 2
20 universal fault signal inputs, "Fault status message delay, Fault
acknowledgement" (none, acknowledge), "Fault priority" (urgent, not
urgent).
2 fault relays, priority (urgent, not urgent, all) and signaling can be set.
Direct connection possible for analog signals and settable threshold
values.
A name can be assigned to each fault input.